Installation Instructions

                    

                    

                    

25-0081

Page 1 of 2

SCHWEITZER ENGINEERING LABORATORIES, INC.

2350 NE Hopkins Court • Pullman, WA 99163-5603  U.S.A.

Phone: +1.509.332.1890 • Fax: +1.509.332.7990

selinc.com • [email protected]

                    

                    

Note: 

The AR360 must detect a minimum voltage field for normal operation. 

Therefore, install the AR360 units at least 2 ft from other line or pole 
hardware when applying these units on phase-to-phase system voltages of 
7.2 kV or less. In addition, be certain not to install any AR360 units in such a 
way as to reduce the insulating air gap between the product surface and any 
other conductor sufficiently to initiate a flashover.

                    

To ensure optimum FCI function, it is best to follow the FCI distance-to-pole recommendations shown in 

Figure 1

.

                    

                    

Figure 1

Reference A: Maximum recommended distance from pole of 6 feet.

Reference B: Minimum distance from pole of 3 feet.

Reference C: Minimum distance from energized hardware of 2 feet.

5.2 in

(13.21 cm)

9.3 in

(24 cm)

3.2 in

(8 cm)

6 in

(15.24 cm)

Before installation, read and understand all instructions in their 
entirety. For assistance, please contact Customer Service at 
1-847-362-8304 or by email at [email protected].

CAUTION

Install in accordance with normal safe operating practices. These instruc-
tions are not intended to replace or supersede existing safety or operating 
requirements. Only trained qualified personnel should install or operate 
fault indicators and sensors.

FCIs

A

B

Note: Not drawn to scale.

C