D.19
Date Code 20100129
Instruction Manual
SEL-751A Relay
DNP3 Communications
DNP3 in the SEL-751A
=>>
SET DNP 1 BO_00 TERSE <Enter>
Binary Output Map
DNP Binary Output Label Name (23 characters)
BO_00 := NA
? >
RB01 <Enter>
DNP Binary Output Label Name (23 characters)
BO_01 := NA
? >
RB02 <Enter>
DNP Binary Output Label Name (23 characters)
BO_02 := NA
? >
RB03:RB04 <Enter>
DNP Binary Output Label Name (23 characters)
BO_03 := NA
? >
RB05:RB06 <Enter>
DNP Binary Output Label Name (23 characters)
BO_04 := NA
? >
end <Enter>
=>>
Figure D.8
Sample Custom DNP3 BO Map Settings
You may also use
AC
SEL
ERATOR
QuickSet to enter the BO map settings as
shown in the screen capture in
Figure D.9
Binary Output Map Entry in
AC
SEL
ERATOR
QuickSet Software
The binary input (BI) maps are modified in a similar manner, but pairs are not
allowed.
Содержание 751A
Страница 1: ...20100129 SEL 751A Feeder Protection Relay Instruction Manual PM751A 01 NB...
Страница 6: ...This page intentionally left blank...
Страница 12: ...This page intentionally left blank...
Страница 18: ...This page intentionally left blank...
Страница 26: ...This page intentionally left blank...
Страница 92: ...This page intentionally left blank...
Страница 218: ...This page intentionally left blank...
Страница 250: ...This page intentionally left blank...
Страница 376: ...This page intentionally left blank...
Страница 392: ...This page intentionally left blank...
Страница 408: ...This page intentionally left blank...
Страница 418: ...This page intentionally left blank...
Страница 434: ...This page intentionally left blank...
Страница 462: ...This page intentionally left blank...
Страница 544: ...This page intentionally left blank...
Страница 580: ...This page intentionally left blank...
Страница 584: ...This page intentionally left blank...
Страница 632: ...This page intentionally left blank...
Страница 636: ...This page intentionally left blank...
Страница 640: ...This page intentionally left blank...