SEL-3355-2 Data Sheet
Schweitzer Engineering Laboratories, Inc.
10
Electromagnetic Compatibility Immunity
Conducted RF:
IEC 61000-4-6:2013
Severity Level: 10 Vrms
Electrostatic Discharge:
IEC 61000-4-2:2008
IEEE C37.90.3-2001
Severity Level:
2, 4, 6, 8 kV contact discharge;
2, 4, 8, 15 kV air discharge
Fast Transient/Burst:
IEC 61000-4-4:2012
Severity Level: Class A
4 kV, 5 kHz on power supply and outputs;
2 kV, 5 kHz on communications lines
Magnetic Field:
IEC 61000-4-8:2009
Severity Level:
1000 A/m for 3 s
100 A/m for 1 m
Power Supply:
IEC 61000-4-11:2004
IEC 61000-4-17:1999+A1:2001+A2:2008
IEC 61000-4-29:2000
Radiated Radio Frequency: IEC 61000-4-3:2006+A1:2007
Severity Level: 10 V/m
IEEE C37.90.2-2004
Severity Level: 20 V/m
Surge Withstand
Capability:
IEC 61000-4-18:2006+A1:2010
Severity Level:
Power supply and outputs
2.5 kV peak common mode
1.0 kV peak differential mode
Communications ports
1.0 kV peak common mode
IEEE C37.90.1-2012
Severity Level:
2.5 kV oscillatory
4 kV fast transient
Surge Immunity:
IEC 61000-4-5:2005
1 kV line-to-line
2 kV line-to-earth
2 kV communications ports
Environmental
Change of Temperature:
IEC 60068-2-14:2009
Severity Level:
5 cycles, 1°C per minute ramp
–40° to +60°C (E3-1505M CPU)
–40° to +75°C (E3-1505L CPU)
Cold, Operational:
IEC 60068-2-1:2007
Severity Level: 16 hours at –40°C
Cold, Storage:
IEC 60068-2-1:2007
Severity Level: 16 hours at –40°C
Damp Heat, Cyclic:
IEC 60068-2-30:2005
Severity Level:
12 + 12-hour cycle
25° to 55°C, 6 cycles, >93% relative
humidity
Damp Heat, Steady:
IEC 60068-2-78:2012
Severity Level:
40°C, 240 hours, >93% relative
humidity
Dry Heat, Operational:
IEC 60255-1:2009
IEC 61850-3:2013
IEC 60068-2-2:2007
Severity Level:
16 hours at 60°C (E3-1505M CPU)
16 hours at 75°C (E3-1505L CPU)
Dry Heat, Storage:
IEC 60255-1:2009
IEC 61850-3:2013
IEC 60068-2-2:2007
Severity Level: 16 hours at 85°C
Free Fall:
IEEE 1613-2009
Severity Level: 100 mm
Vibration:
IEC 60255-21-1:1988
Severity Level:
Endurance Class 2
Response Class 2
IEC 60255-21-2:1988
Severity Level:
Shock Withstand, Bump Class 1
Shock Response Class 2
IEC 60255-21-3:1993
Severity Level:
Quake Response Class 2
Safety
Enclosure Protection:
IEC 60529:2001 + CRGD:2003
Severity Level: IP30
Dielectric Strength:
IEC 60255-27:2013
IEEE C37.90-2005
Severity Level:
3600 Vdc on power supply
2500 Vac on contact output
1500 Vac Ethernet ports
Type tested for one minute
Impulse:
IEC 60255-27:2013
IEEE C37.90-2005
Severity Level:
5 kV common mode, power supply,
contact outputs
1.5 kV Ethernet ports