Control Panel – TEKNA TPR 

 

 

 

 

 

Access to the programming menu 

 

 

 

When pressed during the pump operation phase, it cyclically displays the programmed values on 

the display; When pressed at the same time as the 

 

 keys, it increases or lowers a value 

dependent on the selected operating mode. During programming it carries out an “enter” function, 
meaning that it confirms entry to the various menu levels and modifications within the same. 

 

 

 

Starts and stops the pump. In the event of a level alarm (alarm function only), flow alarm and active 
memory alarm, it deactivates the signal on the display. 

 

 

 

Used to “exit” the various menu levels. Before definitively exiting the programming phase, you will be 
asked if you wish to save any changes. 

 

 

 

Access to the pump calibration menu. If in Off mode, the calibration menu is not activated. 

 

 

 

Used to run upwards through the menu or increase the numerical values to be changed. Can be 
used to start dosage in Batch mode 

 

 

 

Used to run downwards through the menu, or decrease the numerical values to be changed. 

 

 

 

Flashing green LED during dosage 

 

 

 

Red LED that lights up in various alarm situations 

 

 

Electrical connections 

Alarm relay 

3 Pole 

4 Pole 

Exit 4-20 mA 
500 

 max load  

Remote control input (start-stop) 

Temperature probe input 

10

Flow sensor input 

B

B  Input level control 

EM00136063 rev. 

1.0 

1

Содержание TEKNA TPR 600

Страница 1: ...nal on the display Used to exit the various menu levels Before definitively exiting the programming phase you will be asked if you wish to save any changes Access to the pump calibration menu If in Off mode the calibration menu is not activated Used to run upwards through the menu or increase the numerical values to be changed Can be used to start dosage in Batch mode Used to run downwards through...

Страница 2: ...ous programming levels Upon exiting programming the display will show Exit Exit No Save Save to confirm the selection PROG Temperature Man 25 C Probe Calib On Configuration Pump Functions Max flow rate 100 Alarm Relay N Open Language English O F Alarm 0m Resolution 0 01 Alarm Band 2 00 pH Prop Band 0 50 pH Setpoint Type Acid Setpoint 7 00 pH Prog Configuration Pump Functions pH Measure Pump Functi...

Страница 3: ...mode The flow can be manually regulated by pressing the keys at the same time to increase the flow or the keys to decrease it Display during Operation Display during Setting MODE key MAN F F F Lev Stop P100 Operating mode Man Manuel Alarms and statuses Liv Level alarm Fls Debit alarm FLOW sensor status Pump status Empty pump in start Stop pump stationary Paus pump in pause Current dosage value dep...

Страница 4: ...l is triggered if the pH value does not reach the set point The measurement resolution 1 or 2 decimal points Deactivation activation of the calibration procedure Manual temperature value in ºC default or ºF The maximum frequency can be modified during operation by pressing the keys at the same time to increase the flow or the keys to decrease it Display during Operation Display during Setting MODE...

Страница 5: ... at the same time to increase the flow or the keys to decrease it Display during Operation Display during Setting MODE key High F F F 560mV Lev Stop P100 Setpoint type High Low Alarms and statuses Cal calibration not completed Lev Level alarm Flw Flow alarm Alm Measurement outside alarm band OFA O F A alarm Flow sensor status Potential Redox measurement value Pump status Empty pump in start Stop p...

Страница 6: ...ike using the keys and confirm by pressing the key AUTOMATIC the pump makes 100 strikes which are started by pressing the key At the end of this process enter the quantity sucked up by the pump using the keys and confirm by pressing the key The entered figure will be used in flow calculations Paragraph 7 Statistics Programming Operation Statistic Statistic Statistic Statistic Reset Hours 10 Hours ...

Страница 7: ...key and you can then use the keys to set the value Confirm by pressing the key Press to return to the main menu Paragraph 10 Level Alarm Programming Operation Alarm Level Alarm Flow Alarms Level Stop Alarms Level Alarm Stop Alarm PROG ESC This makes it possible to set the pump when the level sensor alarm is activated In other words you can decide whether to stop dosage Stop or simply activate the ...

Страница 8: ...ss the key A 60 second countdown necessary to complete calibration will appear on the display If the alignment quality is below 50 an error message appears on the display and you should press to exit calibration the pump exits automatically after 4 seconds If the quality is above 50 the value is shown on the display and after pressing the key the buffer solution at pH 4 or 9 will be requested At t...

Страница 9: ...ppears on the display Insert the probe in the bottle and press the key A 60 second countdown necessary to complete calibration will appear on the display If the alignment quality is below 50 an error message appears on the display and you should press to exit calibration the pump exits automatically after 4 seconds If the quality is above 50 the value is shown on the display and you should press t...

Страница 10: ...xternal impulses it returns the memorised strokes Fixed alarm LED Flashing word Flw I e Man F Flw P100 Active flow alarm The pump has not received the programmed number of signals from the flow sensor Press the key I e Parameter Error PROG to default Communication error with the eeprom Press the key to restore the default parameters Flashing word OFA Flashing word stop I e High 475 mV OFA Stop P 7...

Отзывы: