background image

 

 

   
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

- ENGLISH - 

TRD03B0000SE 036247 270121 

INSTALLATION 

 WARNING 

Make  sure  that  the  transmitted  radio  signals  are 
correctly received by the receiving unit before installing 
the thermostat. 

-  Install  the  thermostat  at  about  1.5  m  from  the  floor, 

away  from  heat  sources,  draught  and  particularly  cold 
walls  (heat  bridges),  for  the  room  temperature  to  be 
regulated  correctly.  These  notes  must  be  applied  to 
place  the  remote  sensor  when  this  is  used  to  acquire 
the room temperature. 

-  A remote sensor must be connected using wires having 

at least 1.5 mm² section and no longer than 15 metres. 
Do  not  use  the  same  pipes  for  sensor  signals  and 
mains voltage. 

-  The  installation  and  electrical  connection  of  the 

thermostat  must  be  performed  by  qualified  personnel 
and in compliance with current standards. 

Fig. 3

 

Push,  with  the  help  of  a  screwdriver,  the  plastic  tooth 
located  in  the  slot  on  the  left  side,  then  lift  the  plastic 
cover (Fig. 3). 

Fig. 4

 

Turn  the  cover,  while  pressing  it  slightly,  until  it  is  fully 
extracted (Fig. 4). 

Configure  the  thermostat:  see  "INSTALLER 
CONFIGURATION" paragraph.

 

Close the thermostat as follows: 
-  Match  the  two  teeth  located  in  the  right  side  of  the 

plastic  base  with  the  two  slots  located  on  the  plastic 
cover. 

-  Close  the  left  side  of  the  cover  while  slightly  pressing 

with a finger, at the same time, the plastic tooth on the 
left  side  to  the  internal  (see  the  arrow  in  Fig.  8). 
Complete the rotation of the cover until the plastic tooth 
on the base snaps into the relevant hole of the cover. 

Fig. 8

 

Find  the  best  location  for  the  installation  (see  section 
‘RADIO  SYSTEM  CONFIGURATION),  then  secure  the 
thermostat base to the wall using the two screw holes with 
a 60mm. distance (use the screws and/or bolts supplied) 
after  having  passed  the  remote  sensor  wires  (if  present) 
through the rectangular opening (

A

 in Fig. 5).

 

Fig. 5

 

60mm

60 mm

 

 

-  Insert  the  batteries  (respecting  the  correct  polarity)  in 

  the battery compartment (

C

 in Fig. 6); use only alkaline, 

  brand new batteries. 

 

-  Connect  the  remote  sensor  (if  present)  using  the 

  ‘REMOTE SENSOR’ connector (

B

 in Fig. 6), according 

  to the wiring diagram shown in Fig. 7; then remember to 

  set properly the parameter 

P09. 

 

 

Read the section 'INSTALLER CONFIGURATION'.

 

Fig. 6

 

Fig. 7

 

Table 1

: Installer configuration 

Summary of the configuration parameters. 

CON 

Default

 

data

 

End

 

P03

 

-10.0 .. +10.0 

0.0 

OFFSET: Room temperature correction (°C) 

P05

 

5.0 .. 35.0 

10.0 

Temperature Set-point lower limit heating (°C) 

P06

 

5.0 .. 35.0

 

35.0 

Temperature Set-point upper limit heating (°C)

 

 

P07

 

5.0 .. 35.0 

10.0 

Temperature Set-point lower limit cooling (°C)

 

 

P08

 

5.0 .. 35.0

 

35.0 

Temperature Set-point upper limit cooling (°C)

 

 

P02

 

no 

|

 0.5 .. 25.0 

6.0 

Antifrost temperature set-point (°C) 

P04

 

1 .. 10 

Sampling time (minutes) 

P09

 

Remote NTC 

sensor 

Ext 

Internal NTC 

sensor 

Int 

Int 

NTC sensor configuration 

P11

 

no 

reserved parameter 

P10

 

no 

reserved parameter 

P12

 

0.1 .. 5.0

 

0.2 

Hysteresis (°C) 

P13

 

2.0 

reserved parameter 

P14

 

60 

reserved parameter 

P15

 

30 

reserved parameter 

P16

 

reserved parameter 

P01

 

CrO 

Comfort - 

Economy - Off 

CrO 

Economy - 

Off 

rO 

Comfort - 
Economy  

Cr 

Comfort - Off 

C O 

Off 

Economy  

Comfort 

Allowed regulation modes setting 

P17

set-point disp 

YES 

Room T disp. 

no 

no 

Default display of the set-point temperature

 

 

set–point only disp. 

OnL 

Отзывы: