background image

Version No. 1-4 - 31.07.2022

Doc. No. 9943253001

16 / 18

15. Taking into Operation

Attention! The unit can be damaged by lack of lubricant. To ensure that the compressor is adequately
lubricated the oil, which has been displaced during transport, must be allowed to flow back into it. The unit must
therefore be allowed to stand for at least 30 min. before being connected to the mains and taken into
operation. The unit / system must be protected with a MCB Type D or K. 
Upon connection the internal fan will start working. If the temperature inside the enclosure is higher than the
set value of the controller both the compressor and external air fan start working. Once the air inside the
enclosure reaches the set temperature the compressor and external fan will stop.

The hysteresis is 3K, the minimum ON-time is 4 minutes, the minimum OFF-time is 3 minutes, for units with a
cooling capacity of more than 1 kW is it usually 7 minutes.

The unit is pre-set at 35°C, which is suitable for most of the electronic devices.

16. Trouble Shooting

Failure

Condition

Cause

Solution

Unit

doesn't

cool

 Internal fan does not work

 Power not connected.

 Verify power supply

 Internal fan works, external fan
 and compressor don't work

 Enclosure temperature is below
 setting temperature (St1)

 Verify values of parameter  "St1"

Door switch contact is open

 Verify door switch

Controller doesn't work

 Replace controller

 Internal fan works, external fan
 and  compressor don't work.
 Display shows alternating OFF 
 and temperature

 The sequence of the phases
 inside the power supply
 connector is incorrect

 Change phases inside power 
 supply connector

Unit

doesn't

cool

 External and internal fan work,
 compressor does not work

 Compressor motor electrical
 failure

 Have compressor replaced  
 by qualified service technician

 Capacitor for compressor failed  Replace capacitor

 Compressor works, external fan
 doesn't work

 External fan needs to be
 replaced

 Replace external fan

Enclosure

temperature 

too hot

 Compressor and fans (external
 and internal) work all the time

 Cooling unit undersized

 Enclosure needs a cooling unit with higher capacity

 Compressor and external fan 
 work in alternating mode
 (ON / OFF)

 Thermal compressor protector
 triggered 

 Verify if ambient temperature  is too high, clean condenser

 Refrigerant leakage

Contact dealer / service centre

Excessive 

condensate

 Enclosure door open

 Ambient air gets into the  
 enclosure

 Ensure door is closed, add  a door switch and connect
 it to controller

 Enclosure door closed

 Enclosure IP protection class 
 is below IP54

 Seal all openings of the  enclosure

 Damaged or misplaced sealing
 strip

 Repair sealing strip  accordingly

17. Maintenance & Cleaning

Always switch power supply off before starting any maintenance on the unit.

The cooling unit is generally maintenance free and can be operated without filters in most environments. For
units with filters these should be checked, cleaned and if necessary replaced on a regular basis. In addition the
unit should have regular functional tests (approx. every 2,000 hours depending on the grade of ambient
pollution).

Disposal
The unit contains R134a refrigerant and small quantities of lubricating oil. Replacement, repairs and final
disposal must be done according to the regulations of each country for these substances.

Содержание 43253001

Страница 1: ...onal principle 6 6 Technical data 7 7 Performance graph 8 8 Mounting 9 9 Mounting Principle 10 10 Cut Out Dimension 11 11 Dimension H x W x D 12 12 Electrical Connection 13 13 Controller 14 14 Wiring...

Страница 2: ...issipation of heat from control cabinets and enclosures stationary not moving in order to protect temperature sensitive components in an industrial environment To meet the conditions of use all the in...

Страница 3: ...nits based on the information diagrams or descriptions contained in this manual No liability can be accepted for damage and production caused by Disregarding the instruction manual Operating error Ina...

Страница 4: ...regulations One can nd dangerous voltages above 50 V AC or above 100 V DC Behind the control cabinet doors On the power supply in the unit housing The unit has to be operated according to the type pl...

Страница 5: ...air does not come into contact with the ambient air which may well be dirty or polluted Enclosure cooling units can dissipate large quantities of heat from sealed enclosures such as electrical enclos...

Страница 6: ...apillary pipe being a much lower pressure the refrigerant arrived to the evaporator where it absorbs the necessary heat to change from liquid to gas state The gas is then drawn back into the compresso...

Страница 7: ...750 1200 m h Cabinet air circuit 550 1200 m h Mounting Wall mounted Recessed Housing Material Mild steel powder coated Dimensions A x B x C D E 1 230 x 500 x 340 mm Weight 73 kg Cut out dimensions 1...

Страница 8: ...Version No 1 4 31 07 2022 Doc No 9943253001 8 18 7 Performance graph...

Страница 9: ...e case a barrier or duct shall be provided to redirect the air ow Cooling unit enclosure air suction hole must be installed in the highest possible point When installing the unit on a door ensure it c...

Страница 10: ...No 9943253001 10 18 9 Mounting Principle Do not use within the rst 15 minutes after installation 1 M6 screws 2 M6 at washers 3 M6 toothed washers 4 Cabinet 5 Sealing tape 6 Cooling unit 7 Lifting hook...

Страница 11: ...Version No 1 4 31 07 2022 Doc No 9943253001 11 18 10 Cut Out Dimension...

Страница 12: ...Version No 1 4 31 07 2022 Doc No 9943253001 12 18 11 Dimension H x W x D...

Страница 13: ...terminals are bridged on the female connector To connect the door contact switch remove the bridge and connect door contact switch The contact must be closed when the cabinet door is closed SCCR Refe...

Страница 14: ...ress Set to save the new setting To change the heating set point St2 units with internal heater only 1 Press Set till St1 appears on the display and release the button 2 Press again Set till St2 appea...

Страница 15: ...ontroller EB External Blower CE Condensate evaporator 1 Models with condensate evaporator IB Internal Blowers PC 9 Pole connector CC 7 core cable Mc Motor compressor AT Auotransformer 1 400V L1 2 460V...

Страница 16: ...power supply connector is incorrect Change phases inside power supply connector Unit doesn t cool External and internal fan work compressor does not work Compressor motor electrical failure Have comp...

Страница 17: ...ions which meet the following conditions temperature range 40 C to 70 C Relative humidity at 25 C max 95 Returning the unit To avoid transport damage the unit should be returned in the original packin...

Страница 18: ...Seifert Systems AG Seifert Systems GmbH Seifert Systems Ltd Seifert Systems Inc Seifert Systems Pty Ltd Albert Einstein Str 3 HF09 10 Wilerstrasse 16 B rnthal 1 Rep O ce 75 Circuit Drive 105 Lewis Ro...

Отзывы: