8
TB XRI1-IE 11.01 E
3.2.3
Display
Function
Display shows
Pressed push button
Corresponding LED
Normal operation
SEG
Measured operating values
Actual measured values,
<SELECT/RESET>
one time for each
L1, L2, L3, E
Measuring range overflow
max.
<SELECT/RESET>
L1, L2, L3, E
Setting values:
phase (I>; CHAR I>; t
I>
; I>>; t
I>>
)
earth (I
E>
; CHAR I
E
; t
IE>
; I
E>>
; t
IE>>
)
Current settings
Trip delay
Characteristics
<SELECT/RESET>
one time for each
parameter
I >; CHAR I>; t
I>
; I>>;
t
I>>
;
I
E>
;CHAR I
E
; t
IE>
;I
E>>
;
t
IE>>
;
Reset setting (only available at inverse
time characteristics)
0s / 60s
<SELECT/RESET>
<+><->
I>; CHAR I>; t
I>
I
E>
; CHAR I
E>
; t
IE>
Switch failure protection
tCBFP
<SELECT/RESET> <+><->
Tripping protection
switch failure protection
CBFP
After fault tripping
Nominal frequency
f=50 / f=60
<SELECT/RESET><+><->
Switch-over LED flash
No LED flash
FLSH
NOFL
<SELECT/RESET>
<+><->
Blocking of function
EXIT
<+> until max. setting value LED of blocked
parameter
Slave address of serial interface
1 - 32
<SELECT/RESET>
<+><->
RS
Baud-Rate
1)
1200-9600
<SELECT/RESET> <+><->
RS
Parity-Check
1)
even odd no
<SELECT/RESET> <+><->
RS
Recorded fault data
Tripping currents and other
fault data
<SELECT/RESET>
one time for each phase
L1, L2, L3, E
I>, I>>, I
E>
, I
E>>
Save parameter?
SAV?
<ENTER>
Delete failure memory
wait
<-> <SELECT/RESET>
Enquiry failure memory
FLT1; FLT2.....
<-><+>
L1, L2, L3, E
I>, I>>, I
E>
, I
E>>
Save parameter!
SAV!
<ENTER> for about 3 s
Software version
First part (e.g. D01-)
Sec. part (e.g. 8.00)
<TRIP>
one time for each part
Manual trip
TRI?
<TRIP> three times
Inquire password
PSW?
<TRIP><ENTER>
Relay tripped
TRIP
<TRIP>
or after fault tripping
Secret password input
XXXX
<SELECT/RESET>
<+><-><ENTER>
System reset
SEG
<SELECT/RESET>
for about 3 s
Table 3.1:
Possible indication messages on the display, 1) only Modbus