TB MRM3 07.01 E
21
5.9.2 Allocation of the Reset Functions
When setting of the parameters for the blocking func-
tion is completed you are in the allocation mode for
the reset functions. Whether the assigned relay should
be reset manually or automatically after activation or
trip can be allocated to each of the activation or trip
elements. Which of the reset function
•
If necessary the reset function can be changed
with <+> or <-> and saved with <ENTER>
Perhaps a password has to be entered.
•
Proceed to the next function with
<SELECT/RESET>
•
After selection of the last reset function settings for
the 2
nd
parameter set can follow.
•
For allocation of the output relays press push-
button <SELECT/RESET> again. (See next chap-
ter).
Symbol
Protective Functions
Default
Setting
Possible Settings
LED/Colour
ϑ
>
Overload warning
AUTO
HAND ; AUTO
ϑ
> red
I
B
>
Overload alarm
AUTO
HAND ; AUTO
I
B
>
green
I
B
> +
τ
W
Overload trip
AUTO
HAND ; AUTO
I
B
>
green/
τ
W
green
I<
Undercurrent alarm
AUTO
HAND ; AUTO
I< red
tI<
Undercurrent trip
AUTO
HAND ; AUTO
I< red / t> red
I>
Overcurrent alarm
AUTO
HAND ; AUTO
I> red
tI>
Overcurrent trip
AUTO
HAND ; AUTO
I> red / t> red
I>> Start
Short-circuit alarm when starting
AUTO
HAND ; AUTO
I>>red / Start
green
I>> Start
Short-circuit alarm
AUTO
HAND ; AUTO
I>>red
tI>>
Trip of short-circuit element
AUTO
HAND ; AUTO
I>> red / t> red
I2>
Load unbalance alarm
AUTO
HAND ; AUTO
I2> red
tI2>
Load unbalance trip
AUTO
HAND ; AUTO
I2> red / t> red
I
E
>
Earth current alarm
AUTO
HAND ; AUTO
I
E
> red
tI
E
>
Earth current trip
AUTO
HAND ; AUTO
I
E
> red / t> red
tCBFP
CB failure protection
AUTO
HAND ; AUTO
CB green
Trip
External trip
AUTO
HAND ; AUTO
Trip red
Table 5.5: Default setting of the Reset Functions