background image

 

SEQUENCER WITH 

DIFFERENTIAL PRESSURE 

SWITCH

 

 

 

Technical brochure               

  FI 72.0483.0720E 

 

   Page 8 sur 43 

- 8 -Page 8 sur 43 

- 8 -  - 8 - 

- 8 - 

- 8 - 

 

DIMENSIONS AND MOUNTING (ATEX version) :  

Only version SV Pmax=25VA

     

 

Main Box  /  front side, right side and left side :

 

 

 

On the underside of the box: 

SV connection area 

see next page 

1  2 



10 

11 

12 

13 

14 

supply

 

extension com

 

CDM com

 

customer com

 

dP - pressure connection  
(clean air side) 
Connection for 6/8mm tube

 

dP + pressure connection  
(dirty air side) 
Connection for 6/8mm tube

 

Compressed air pressure connection 
Connection for 4/6mm tube        (A/C)

 

4-20mA output dP

 

4-20mA output A/C 

10 

AON input I4 

11 

relay outputs 

12 

AON input I2 

13 

AON input I3 

14 

AON input I1 

 

Содержание SET100DP

Страница 1: ...Technical brochure FI 72 0483 0720E Page 1 sur 43 Outputs SV AC version Not ATEX version ATEX version ABS Box PC Box PLACE GUTENBERG 59175 TEMPLEMARS France Tel 33 0 3 20 60 49 49 Fax 33 0 3 20 95 59...

Страница 2: ...RTU fieldbus Possibility of external gateway to other bus for example PROFIBUS DP The device is adjustable according to the use of it with several levels protected by passwords All the running paramet...

Страница 3: ...1A to be protected by user Ambient operating temperature not ATEX version 20 60 C ATEX version 20 C 55 C Storage temperature 20 to 70 C Box ABS material IP65 not ATEX version PC material IP65 ATEX or...

Страница 4: ...1 5 on sensor maxi scale 10 Bar from 0 to 50 C this accuracy takes into consideration linearity hysteresis temperature and repetitivity effects humidity 0 to 95 RH not condensed response time operati...

Страница 5: ...Compressed air pressure connection Connection for 4 6mm tube A C 4 ISO16 4 20mA output dP 5 ISO16 4 20mA output A C 6 ISO16b AON input I1 7 ISO20b relay outputs 8 ISO16b AON input I2 9 ISO16b AON inp...

Страница 6: ...nsion Box undersize of the box Individual cables version 1 common ground per SV 18xISO16 Multiconductors cables version 3 common 3 ground for 3x6 EV 3xISO20b Multiconductors cables version if version...

Страница 7: ...al brochure FI 72 0483 0720E Page 7 sur 43 SV extension box 1 ISO20 supply 2 ISO16b extension com input 3 ISO16b extension com output Main box or SV extension box behind side of the box On the undersi...

Страница 8: ...connection area see next page 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 supply 2 extension com 3 CDM com 4 customer com 5 dP pressure connection clean air side Connection for 6 8mm tube 6 dP pressure connec...

Страница 9: ...common ground per SV 18xISO16 Multiconductors cables version 3 common 3 ground for 3x6 EV 3xISO20b Clamping capacity of the cable glands Identify the cable glands used by the markings on the cable gla...

Страница 10: ...AL PRESSURE SWITCH Technical brochure FI 72 0483 0720E Page 10 sur 43 SV extension box front side right side and left side note undersize of the box same as main box 1 supply 2 extension com input 3 e...

Страница 11: ...fuse F3 caliber F1A F1A If version Pmax SV 45VA Supply voltage 230VAC 115VAC Solenoides valves voltage 230VAC 48VAC 24VAC 115VAC 48VAC 24VAC fuse F1 caliber F1A F1A fuse F2 caliber F1A F1A fuse F3 ca...

Страница 12: ...the device must be switched off Notes The supply choices 115V 230V or 24 48V can be made only with order If supply voltage 115V 230V the voltage choice of solenoid valves 24V or 48V can be made only w...

Страница 13: ...3 sur 43 230VAC 24VAC 230VAC 48VAC 115VAC 24VAC 115VAC 48VAC WARNING a modification of the supply voltage and or the solenoid valves voltage requires to update the descriptive label placed outside of...

Страница 14: ...ection between 0 5 and 1 5 mm2 Power supply of the device The power supply for the device is connected in the upper part to the left of the board Communication extension CDM customer These connections...

Страница 15: ...for recorder indicator etc max load 500 ohms Relay output K4 Run order report AON input I4 Forced running Relay output K3 High alarm dP AON input I1 Run order AON input I2 Compressed air control A C R...

Страница 16: ...ed at the bottom and center of the board If version up to 18 SV by individual cable 1 common ground per SV If version up to 18 SV by multiconductors cable 1 common ground for 6 SV Connection of the ou...

Страница 17: ...rsion with possibility of connection of two SV per output if version pmax SV 40VA 6 common 6 ground for 6x6 SV 6x common SV 6x ground SV Connection of the outputs solenoid valves 1 to 18 Each connecti...

Страница 18: ...e rotary switch encoder in front of the associated number 1 to 8 Notes the connection of the power supply of the extension boxes is the same that the main box the connection of the SV outputs of the e...

Страница 19: ...xcept when displaying the load loss dP Compressed air A C or rejection CDM pages Main page if no fault Main page if fault 1 Display of the measure of the load loss dP in daPa If a high or low dP alarm...

Страница 20: ...f this area flashes red If press on this area link to the page Compressed air A C Note This area is not displayed if the device does not have this feature 9 Display of status of the operating compress...

Страница 21: ...rage measured over this time see note 1 3 Display of measured values of the minimum and maximum pressure load loss dP observed Notes the minimum value is observed two minutes after the detection of th...

Страница 22: ...30 operating points of the device 1 new point is added according to the value of the set step When the power is turned off the graphic is reset 2 Setting the graph advance 1 to 255 seconds Each time t...

Страница 23: ...e graph advance 1 to 255 seconds Each time this timer expires a new point is added to the graph The value of the added point is the average measured over this time see note 1 3 Display of the instanta...

Страница 24: ...5 counter of cycles done manufacturer 6 If press on this area return to main page 7 Displays the current protection level 8 reachable only at level 1 If press on this area the counter number of user c...

Страница 25: ...o parameters menu page 5 if press on this area jump to system info page 6 if press on this area jump to manual running page 7 displays the current protection level Language page 1 if press on this are...

Страница 26: ...he possibility to reset some counters for instance 1 If press on this area request to enter the password Depending on the password entered the corresponding level is activated Note If the password ent...

Страница 27: ...rs of the compressed air A C control 4 if press on this area access to the parameters related to the fan function 5 if press on this area access to the parameters of the rejection control CDM 6 if pre...

Страница 28: ...hours which is adjusted the ongoing cycle is stopped if stop in cycle and a declogging cycle is launched Note the presence of compressed air is necessary for this operation Remark T4 time is reset at...

Страница 29: ...always in normal running Note An accelerated running request can also be given with the AON I3 input 5 Threshold High Alarm dP reachable at level 1 or above If measure dP is above this threshold more...

Страница 30: ...The output is at 4mA if the load loss dP measure 0 daPa The output is at 20mA if the load loss dP measure indicated value Between 4 and 20 mA the output is linear and proportional to the load loss dP...

Страница 31: ...e control is done with compressed air measure A C A C input the control is done with the state of the AON input A C I2 2 Choice of the control or not of the presence of compressed air out of decloggin...

Страница 32: ...n of the fault in the main page INFLAT A C Svx where x is the number of the faulty SV This fault is auto reset when the control returns to OK 6 Operating threshold adjustable from 0 0 to 6 0 Bar reach...

Страница 33: ...at 4mA if the compressed air A C measure 0 daPa The output is at 20mA if the compressed air A C measure indicated value Between 4 and 20 mA the output is linear and proportional to the compressed air...

Страница 34: ...e stop of the fan is detected if I1 0 Note the running of the fan is detected if input I1 1 by dP loss the stop of the fan is detected if the load loss dP measure is lower than the value indicated on...

Страница 35: ...and above n2 x PR ALARM see CDM instructions 3 Setting the x parameter of the rejection controller CDM from 1 to 33 reachable at level 1 and above x average duration see CDM instructions 4 Launching...

Страница 36: ...ment of the number of SV used in the main box from 0 to 18 reachable at level 1 and above 3 to 10 Adjustment of the number of SV used in extension boxes 1 to 8 from 0 to 18 reachable at level 1 and ab...

Страница 37: ...247 reachable at level 1 and above 2 Speed setting reachable at level 1 and above 2400 4800 9600 19200 38400 57600 or 115200 3 Type setting reachable at level 1 and above 8N1 8 bits no parity 1 stop 8...

Страница 38: ...rmed independently of the input I1 the load loss dP pressure measure the input I2 the compressed air measure A C The value is downcounted as the cycles are done 2 Setting an SV number to activate it m...

Страница 39: ...ompressed air is lost the cycle stops at the end of the idle time The cycle will resume when the compressed air reappears at the solenoid valve where it was stopped If detection of fan stop by input I...

Страница 40: ...fault ELECTRIC FLT Svx if electrical fault on SV with x SV number If it is an installation with extension boxes short circuit electrical faults are identified by ELEC FLT SC Main If short circuit elec...

Страница 41: ...if there is no fault or alarm contact between the terminals identified OUT1 and NO1 The relay is not energized if there is a fault an alarm or if the device is switched off contact between the termina...

Страница 42: ...maxi pressure value of the range Adjustments made when device stabilised and at 20 C It is possible to adjust the zero pressure see load loss dP parameters WARRANTY The warranty does not apply in the...

Страница 43: ...l regimes TT TN or IT Nevertheless we recommend that the device is supplied through the intermediary of an insulation transformer for which the primary is supplied between phases and not between phase...

Отзывы: