SEELEY INTERNATIONAL
- SERVICE GUIDE
|
21
MAGIQCOOL CONTROLLER -
ENTERING PARAMETER MODE
To enter Parameter mode, the following
process must be carried out within 4 minutes
of power being applied to the cooler. If unsure
of time since the last power “ON”, remove
power to the cooler (Isolator Switch or Circuit
Breaker) for a minimum of 6 seconds so the
mode can be entered.
1. While wall control is OFF, push and hold
“
” and “
” button for minimum
three (3) seconds.
2. When parameter mode has been entered,
screen will display “A1” and “Param”.
Pressing “
” or “
” buttons will
scroll through parameters “A1” to “AA”
(Refer to table for factory settings).
3. To view parameter number set in wall control
press “
” momentarily. Figure “A#”
on screen will change to number set, and
“Param” will change to “value”.
4. To alter “value” of selected parameter press
“
” or “
”. Numbers will change
to show different values the parameter can
be set to.
5. To store the value, press “
”. Screen
will go blank momentarily as wall control
stores parameter change, and returns
screen to “A#” and “Param”.
6. To exit parameter mode or escape from an
alteration without storing a change press
“
” button instead of “
” button.
Remember, once step 5 has been carried
out, new parameter change is permanent
until again altered.
7. If no buttons are pushed on wall control,
after 3 minutes screen will reset to “OFF”
state. Procedure to enter parameter mode
must be re-initiated.
Parameters
No. Description
Value
A1
Water salinity control method
selector:
Water Manager
(measure & control salinity)
Timed Drain
Non Drain Valve salinity control
(bleed etc)
No Water, thermostatic vent, Auto
temp control
0*
1
2
3
A2
Weather Seal Opening Speed
Whenever the fan is turned ON,
Fan will run 10 seconds at the
higher of:
Fan Speed as requested by the
Wall Control
Weather Seal Opening Speed set
at A2 (Default = fan speed 5)
A3
Pre-wet enable:
No pre-wet
Pre-wet
0
1*
A4
Wall Control back light disable:
Backlight ‘OFF’
Backlight ‘ON’
0*
1
A5
Conductivity set point:
Normal - 4275 µS/cm
Low - 2305 µS/cm
0*
1
A6
Tank (reservoir) drain delay:
Drain 3 hours after COOL off
Drain 12 hours after COOL off
Drain 3 days after COOL off
1
2
3*
A7
Auto re-start after Power failure:
Requires manual re-start when
power OFF
Auto restart
0
1*
A8
Temperature units:
Display °C
Display °F
0*
1
A9 Not Accessed
AA Not Accessed
* = Default Value