SEELEY INTERNATIONAL –
OWNER’S MANUAL
®
CPL LCB BM Evaporative Cooler
®
SERVICE
“SERVICE”
immediately on power
up indicates
communications needs
to be established
Push & hold the
button for at
least 10 seconds until
the word
disappears
“DOWN”
“SERVICE”
10
PROBLEM – Unpleasant Odour
CAUSE
ACTION
1.
Odour from new pads.
Allow time to condition by running the air
cooler. Drain the water, then allow the tank to
re-fill.
PROBLEM – Inadequate Cooling
CAUSE
ACTION
1.
Dry pads.
Check water flow to pads.
Inspect fitment of distributor cap.
Check for blocked or kinked hose. If blocked,
dismantle, clean and flush or un-kink the hose.
2.
Insufficient exhaust openings for
conditioned air.
Ensure sufficient openings. Refer to chart on
Pg. 2
3.
Excessive ambient humidity
(See also Insufficient exhaust)
On days where the ambient humidity is high,
the cooler will not reduce the temperature as
much as on drier days.
If your wall control displays SERVICE or should you consider that your cooler requires service, contact
your local Dealer or the Service number on the back of this manual.
Note!
If on initial start up the word “Service” appears on the controller and by pushing the on/off button
nothing happens, then you will need to establish communication between the wall control and the
electronic controller. Simply push and hold the “DOWN” button for approx. 10 seconds or until the
word “Service” disappears. If by pushing the on/off button a number appears, contact your local
Dealer or the Service number on the back of this manual.
TROUBLE-SHOOTING GUIDE
ROUTINE MAINTENANCE SERVICE SCHEDULE CHECKLIST
Service Item
Check/adjust
Clean
Replace
1 2 3 4 5 1
Water Distribution System
Component Function
General Operation
Chillcel pads (replace as required)
Pad retaining washers / pins
Base / water reservoir
Pump filter basket
Water probes
Water distribution system
Washers, seals and O-rings (replace
as required)
Drain operation
Bleed rate set (where required)
Pump operation
Drain valve operation
Motor operation (set motor amps
where required)
Solenoid operation
Wall control operation
Water level set point
Water fill time
Water drain time
Water distribution across pads (no dry spots)
Airflow through system / outlets
General product condition
Service No
Service Date
Service Technician
Service Company
No 1
.....................
..........................................
........................................................
(includes correct fitting of all components and items -
replace as required)
2 3 4 5 1 2 3 4 5
No 2
.....................
..........................................
........................................................
No 3
.....................
..........................................
........................................................
No 4
.....................
..........................................
........................................................
No 5
.....................
..........................................
........................................................