14
another hour. Then the temperature remains constant for 10 hours. The screen is
dimmed. The fan speed is set to the lowest level for quiet operation and is not
adjustable.
5.3.3 Timer adjustment (1 -24 hours):
Deactivate
(Unit in)
Light
(Output unit)
Erase
5.3.4 Automatic defrosting
At low ambient temperature, frost can form in the evaporator during operation. The
device automatically starts to thaw and the on/off light flashes. The defrosting sequence
is as follows:
A.
When the unit is operating in cooling or drying mode, the ambient temperature
sensor detects that the temperature of the evaporator coil is below -1 ° C. Once
the compressor has been turned off for 10 minutes or the battery temperature has
reached 7°C, the device will return to cooling mode.
B.
When the unit is operating in heating or drying mode, as soon as the evaporator
temperature sensor detects a temperature below 40 ° C and the temperature
difference between the evaporator temperature and the ambient temperature is
less than 19 ° C, after the compressor has been running for 20 minutes, the unit
begins to thaw for 5 minutes and the operating light flashes.
Press
Hours
to
activate the timer
function.
Press
Hours
to turn off
the timer feature.
.
Press
Up/Down
to set
the downtime.
Press
Up
/
Down
to
set the AN time.
Press the
Up/Down
key repeatedly until the LED shows "00".
Note: Pressing the
POWER
key also completes the timer
setting.
ENG