ANGLED WALL RADIATION SHIELD (RSM+, RSMI30, RSMI45)
When traversing a combustible wall with the chimney at a 30º or 45º angle, an angled firestop
or wall radiation shield must be installed. Only one is required.
Note: 45º angle for Canada only
In cold climate locations, we recommend that you use the insulated wall radiation shield since
it will maintain the home’s thermal barrier.
RSM+ and RSMI30, RSMI45
CHIMNEY MODEL
ANGLE
HOLE SIZE
ASHT+ / (6" dia.)
30º
283 mm x 781 mm (11 1/8" x 30 ¾")
Canada only
45º
283 mm x 518 mm (11 1/8" x 20 3/8")
S2100+/ (6" dia.)
30º
327 mm x 881 mm (12 7/8" x 34 11/16")
AC (6" dia.)
30º
380 mm x 972 mm (15" x 38 ¼")
Table 5
Figure 33