Page 10 of 40
BGX701-014-R03, User Manual for PT3 Transducers
Public
5 Technical specifications
Environmental and safety specifications
Protection class
II (double insulation) EN 61010-1
Pollution degree
2
Ingress protection
Protection enclosure - IP 40, terminals and USB - IP 20
(EN 60529)
Temperature
Operating range
-5
°
C to + 55
°
C
Limit range for
storage
-25
°
C to +70
°
C
Limit range for
transportation
-25
°
C to +70
°
C
Temperature
coefficient
± 0.1% / 10
°
C
Reference conditions
Usage group (IEC
60688)
Group I
Reference
temperature range
+10
°
C to + 35
°
C
Pre-conditioning
30 minutes
Environment
Indoor only
Humidity
95% non-condensing
Altitude level
Up to 2000 m
Over voltage / Installation category
CAT III for
≤
300 VAC and CAT II for
≤
600 VAC
Measurement category
CAT III for
≤
300 VAC and CAT II for
≤
600 VAC
Insulation AC voltage test (IEC 61010:2010)
3.7kV
Impulse voltage test (IEC 61010:2010)
6.4kV
Electrical specifications
Transducer variant
Parameter
Specification
AC
voltage
Input voltage (U
n
)
100 V to 500 V (L-L)
500 V is maximum limit.
Measuring range
0 to 130% U
n
Scale factor
0.8 to 1.5 of U
n
(up to 500 V)
Frequency
50/60 Hz (±5%)
Maximum overload voltage 1.3 x U
n
continuously
2 x U
n
for 1 second, with up to 10 repetitions at 10 second
intervals
Output curve
mA
type
0-20 mA, 4-20 mA and 0-10 mA
(Applicable for accuracy class 1.0, 0.5 and 0.2)
0-5 mA