ZONE PROGRAMMING

Zones, in the context of an alarm system, are individual 

detectors

. If the alarm gets triggered, the system records the zones that were 

tripped, allowing

 the

 user to know the exact point of action. Zones also help the monitoring station to know whether they should call the 

police or fire department upon an alarm. Each zone must be assigned to a partition.

Service Mode 

}

System Setup 

}

Zones

It is recommended to give a

n

 

appropriate

 name to the zone. This name will be used by the system for SMS   

sending or 

for display

 on keypad

’s 

 LCD 

screen 

and etc. 

Page 4

Short  programming manual - basic information 

Intruder alarm system

|

Operation mode  

}

 Small System

The meaning of LED indication depends on module operation mode:
     

Small System 

(up to 3 partitions)

 - 

this operation mode is useful when the

 

system has 1 or 2 partitions 

enabled.

       

1st and 2nd module LED indicates the arming mode in 1st and 2nd partitions respectively;

       

3rd LED indicates system troubles;

       

4th LED indicates an alarm, an alarm memory

,

 

n

ot ready status

 (open zones), 

and zone bypass.

If the system has 3 partitions enabled, then 

the 

3rd LED will indicate the arming mode of the 3rd partition. 

Troubles will be indicated on the 4th LED. Color meaning:

       

Red color - Alarm;

       

Red slowly blinking - Alarm memory;

       

Green color - Not Ready;

       

Yellow color - Trouble;

       

Blue color - Bypassed Zone.

     

Large System

 (4 partitions)

 - 

each partition is assigned to the different module’s LED. Module LED indicates 

all information (arming mode, alarm, alarm memory, troubles

,

 and zone bypass).

Z01

|

Name         

}

Entry Door

Z01

|

Address      

}

Z01

|

Address      

}

Z01

|

Address      

}

00_1

00_1 A

00_1 B

Z01

|

Loop Type   

}

 NC/DEOL

Z01

|

Partition    

}

 1

Z01

|

Definition   

}

 Entry/Exit

Zone address is a 3-digit number represented in 

MA_Z 

format

,

 where 

MA

 specifies a module address in the 

system and 

Z

 specifies a zone terminal in 

the

 

module board. Example: 

00_1

 - 

where 

00 means the control panel 

and 1 means the zone terminal Z1.

 

T

o program 

doubled zon

e - 

 A and B detectors must be specified. Use 

keypad keys [A] or [B] to specify theses detectors in zone address field (example: 00_1 A, 00_1 B, ...).

Note:

 use loop types 

NO/DEOL

 or 

NC/DEOL

 for the doubled zones.

For wireless zones MA_1 – MA_8 the system will automatically   assign 

NO/DEOL

 loop type and for wireless 

zones MA_9 – MA_16 the 

Vibration

 loop type. Do not change the loop type of zone!

Wireless m

odule address

:

   

  EXT116S - 

address

 

06

 (

default

or one that is given during the registration process.

 

Virtual 

wireless 

module EXT116S address:

     

P16 - 

address

 

12

;

     

P32 - 

address

 

12

 

and

 

13

.

The 

Loop type

 menu enables you to program the connection type used for each of the system’s zones. The 

actual (physical) loop type for each zone must comply with that selected in the 

Loop type

 menu. Available loop 

types:

 

 

Not used

 

     

NC - 

uses normally closed contacts and no end of line resistor;

     

NO - 

uses normally open contacts and no end of line resistor;

     

uses normally closed (NC) contacts in a zone terminated by a 1k end of line resistor;

NC/EOL - 

     

uses normally open (NO) contacts in a zone terminated by a 1k end of line resistor;

NO/EOL - 

     

 

uses normally closed (NC) contacts in a zone using at least two 1k end of line resistors to 

NC/DEOL -

distinguish between alarms and tamper conditions;
     

ses normally open (NO) contacts in a zone using at least two 1k end of line resistors to 

NO/DEOL - 

u

distinguish between alarms and tamper conditions;
     

Vibration - 

special purpose zone loop type;

     

Roller

 - 

special purpose zone loop type;

Each zone must be assigned to a partition. 

 

All zones are assigned to 

the 

1st partition by default.

Setting the zone definition is partly determined by the arming mode:
     

Entry/Exit

 - used for Entry/Exit doors. A zone must be closed during arming and when the delay expires. 

Entry delay will be available when

 the

 system is armed in 

Away

 or 

Stay

 mode. 

     

Interior - 

usually assigned to motion detectors and to interior doors. Violation of this zone will not trigger an 

alarm when 

the 

system is armed in 

Night

 or 

Stay

 mode.

     

Perimeter 

or

 Instant

 - usually intended for non-exit/entry doors, window protection, shock detection, and 

motion detectors.  A zone goes immediately into an alarm state when violated while armed.
     

24h Burglary

 - a violation of such a zone causes an instant intrusion alarm, regardless of the system’s state.

     

24h Panic Silent 

- used for external panic buttons. If violated, an immediate panic alarm is triggered, with the 

exception that there is no audible indication of the violation.
     

24h Panic Audible

 - same as 

Panic Silent

, except that the

  

alarm will be audible.

     

24h Tamper - 

the tamper function is continuously operational. When a 

24h tamper

 zone is activated, a 

tamper alarm is generated.
     

24h Fire

 or 

24h Smoke - 

for smoke or other types of fire detectors. To avoid false alarms, zone attribute 

Fire 

Verification

 is recommended to use.

     

24h Fire button

 - for external auxiliary emergency alert buttons. If violated, an immediate fire alarm will 

sound, regardless of the system’s state.
     

24h Medical button - 

for external auxiliary emergency alert buttons. If violated, an immediate medical alarm 

will sound, regardless of the system’s state.

System with  

KM2

0B

 

keypads

Содержание KM20B

Страница 1: ...send the default template or customized project to the control panel and all successfully registered system modules Press the ENT key Template is being sent to the system Registration of modules is i...

Страница 2: ...ddress which is used by another module then the new module will overtake this address and the other module will stay unregistered Note a registered module will slowly flash its address on a green LED...

Страница 3: ...counting when the module is installed indoors or outdoors If proximity reader is installed outdoors then the entry exit delay is excluded The preferred arming mode will appear as a first option With...

Страница 4: ...s module EXT116S address P16 address 12 P32 address 12 and 13 The Loop type menu enables you to program the connection type used for each of the system s zones The actual physical loop type for each z...

Страница 5: ...arms Z01 Attributes Fire Verific Z01 Attributes In Exit Rout Z01 Attributes In Entry Rou Z01 Attributes Arm on Exit Z01 Attributes No alarm Z01 Attributes Bypass Enabl Z01 Entry Delay 30 seconds Z01 P...

Страница 6: ...on the selected technical zone SelectedAlarms output activates if a selected type of alarm occurs on the selected partition Chime output activates if the selected zone is violated when the system is...

Страница 7: ...ll call again Program the Account number This account number will be used for all reporting events Use the key to enter additional hex symbols B C D E F Value programmed in this parameter determines h...

Страница 8: ...et and the LAN module will automatically find that IPaddress on the internet The Time Settings menu contains parameters that enable the routing of periodic test event to CMS receivers Service Mode Rep...

Страница 9: ...nu enables you to assign the partition s in which the user except for the 1st system user will operate Used to allow users to control the system during predefined time periods Note if the timer is not...

Страница 10: ...modules The message First Start Press ENT will appear on keypad s LCD screen when this procedure will end If entered the control panel will start uploading the project to all registered system modules...

Страница 11: ...Sessions PauseBTWsessio Dial Tone Test Method LineMonitoring LineLossDelay SERIAL Interface GPRS settings LAN settings APN User name Password Obtain IPauto Obtain DNS auto IPaddress Subnet mask Gatewa...

Отзывы: