to PGM /
relay
Normally closed
contact
(NC)
Normally closed
contact with one
resistor
(NC/EOL)
Normally closed
contact with two
resistors
(NC/DEOL)
Normally open contact
(NO)
Normally open contact
with one resistor
(NO/EOL)
Normally open contact
with two resistors
(NO/DEOL)
Wiring of zones
Detector
+AUX COM
Z1 COM
GSV4
+
A
U
X
C
O
M
Z
1
C
O
M
Tamper
1k
Ω
+AUX COM
Z1 COM
+
A
U
X
C
O
M
Z
1
C
O
M
GSV4
Tamper
Detector
1k
Ω
1k
Ω
GSV4
+AUX COM
Z1 COM
+
A
U
X
C
O
M
Z
1
C
O
M
Tamper
Detector
GSV4
+AUX COM
Z1 COM
+
A
U
X
C
O
M
Z
1
C
O
M
Tamper
Detector
1k
Ω
GSV4
+AUX COM
Z1 COM
+
A
U
X
C
O
M
Z
1
C
O
M
Tamper
Detector
1k
Ω
1k
Ω
GSV4
+AUX COM
Z1 COM
+
A
U
X
C
O
M
Z
1
C
O
M
Tamper
Detector
Wiring of a 4-wire smoke detector
Note:
Smoke detectors produ-
ced by different manufacturers
may have a different terminals
layout. For more information
check detector wiring manual
provided by the manufacturer.
Terminals of smoke detector
3
4
2
6
5
to COM
to zone
to COM
Smoke detectors can be triggered by dust. Therefore, in order to prevent false alarms, it
is recommended to perform a fire alarm verification. Certain system settings must be
activated for the verification.
Zone settings:
Zone
definition:
24h smoke;
Attribute assigned to the zone:
Fire verification
;
PGM output settings:
Fire (smoke) detector must be powered from PGM BELL. If +BELL is
occupied, the power to the detector should be supplied from +AUX via relay. The relay
should be controlled by -PGM1 or -PGM2 ;
PGM
definition:
Fire Power Supply
;
Zone selected to be as a fire zone must be marked as a trigger source for PGM output;
PGM reset time must be set;
Global time settings:
Detector settle time
must be set;
Fire zone verification time
must be set;
Operation:
In order to check the triggered fire detector, power supply of the detector has
to be turned off temporarily and turned on again. The PGM output's length of time that it
stays turned off can be set under the setting
Reset time
. When reset time expires, the
system turns ON the PGM output again and waits for the detector to settle (
Detector
settle time
). Then the system checks the detector again as long as it was set under the
Fire zone verification time
. If the fire detector is triggered again, it means that the alarm
was real.
It is recommended to use diode to
supress voltage surges on relay.
Wiring of relays
D1
NC
NC NO
NO
Relay
GSV4
+AUX -PGM1
+
A
U
X
-P
G
M
1
D1
NC
NC NO
NO
Relay
GSV4
+BELL COM
+
B
E
L
L
C
O
M
Additional information
System start-up with no 230V AC
power
Connect 12V battery with
G S V 4 b y u s i n g B AT
connector. Use a jumper to
close (for a short time)
terminal pins. The system
will start to operate,
however, AC loss trouble
will be indicated.
12V batery
7Ah/20HR
Black
Red
C
O
M
A
C
B
A
T
2
0
V
+
B
E
L
L
Jumper
Restoring user PIN to default value
Purpose of S1 and S2 buttons
GSV4 has two buttons on a board: S1 and S2. The purpose of each button depends on whether its module is working (powered) or not (not powered):
when the device is working, S1 and S2 buttons are used to enable a service mode, register, download and upload the project at www.alarmserver.net. Pressing
each button certain amount of times corresponds to a specific function described in pictures below:
1 x S1
Enable service mode
(10 min.)
2 x S1
Upload project to
www.alarmserver.net
3 x S1
Register system at
www.alarmserver.net
2 x S2
Download project from
www.alarmserver.net
when the device is not working, S1 button is used to start a firmware upgrade process. The firmware upgrade mode can be turned on by pressing and holding S1
button and connecting USB cable at the same time. The software
Firmware Upgrade Tool. V.1.xx
is used to upgrade the firmware.
Intruder alarm system
GSV4
Wiring manual
Zones settings:
Global time settings:
PGM ouput settings:
In order to restore user’s PIN to default
value, it is necessary to change some
settings:
Connect
GSV4
to a computer via USB.
Download the project with the help of the
MASCAD software.
Open a
Users
tab and select a user that
forgot his/her PIN. Select the
Temporary
PIN
check-box. Default PIN is shown in
brackets.
Save settings and upload them back to
GSV4.
12V
C
T2
NC
T1
T
1
T
2
N
C
C
12V
C
T2
NC
T1
T
1
T
2
N
C
C
12V
C
NC
T2
T1
T
1
T
2
N
C
C
12V
C
T2
NO
T1
T
1
T
2
N
O
C
12V
C
NO
T2
T1
T
1
T
2
N
O
C
12V
C
NO
T2
T1
T
1
T
2
N
O
C
Page 3