The programming and  deleting procedure is the same as the 
one illustrated  above except that  the led selected  should  be 
CODE PED.

5)  MOTOR TIME and DECELERATION:

 

(Programming a motor 

operation time of max 4 minutes)

The control unit is supplied by the manufacturer with a default 
motor operation time of 30 seconds, without deceleration.
To modify the operation time of motors 1 and 2, proceed as 
follows when the gate is closed: use the SEL key to navigate to 
T.MOT  when   the  respective   LED  is   flashing,   then   press   the 
SET key briefly and motor 1 will begin its opening cycle; when 
the initial point of deceleration is reached press the SET key 
again: the T.MOT LED will start flashing more slowly and motor 
1 will decelerate; when the desired position is reached, press 
the SET key to complete the opening cycle. The T.MOT LED 
now starts flashing normally again and motor 2 will begin its 
opening cycle; program the work time for Motor 2, following the 
same   instructions   as   for   Motor   1.     After   programming   the 
opening times for the motors, motor 2 will start its closing cycle: 
repeat   the   same   instructions   as   above   for   programming   the 
closing cycle of motor 2 and then for motor 1.
To   deactivate   the   deceleration   function   during   programming, 
once  the  opening  and  closing  cycle   is  completed,  press  the 
SET key twice in succession instead of just once.
If you use the control unit in the configuration with the 1 Motor 
LED 1-2 MOTORS OFF, you do not need to program the work 
time for Motor 2.

When programming, you can use the radio control key on the  
control unit instead of the SET key, if stored previously.

6) T. MOT. PED:

 

(Programming pedestrian operation time of max 4 

minutes)

The control unit is supplied by the manufacturer with predefined 
operation time of Motor 1 (Pedestrian) of 10 seconds without 
deceleration.
To modify the pedestrian operation time, follow this procedure 
with the shutter closed: with the SEL key go to T.MOT.PED. 
LED when flashing, then press the SET key rapidly, Motor 1 
starts the opening cycle; when the initial point of deceleration is 
reached press the SET key again, the motor decelerates until 
the desired position is reached, press the SET key to complete 
the opening cycle. The T.MOT.PED LED starts flashing rapidly, 
now   repeat   the   programming   operation   for   closing.   To 
deactivate the deceleration function, during programming, once 
the opening and closing cycle is completed, press the SET key 
twice in a sequence.

During programming the radio control key of the control unit  
can be used instead of the SET key, if stored previously.

7) T. PAUSA:

 

(Programming the aut. Closing time – 4 min max.)

The   control   unit   is   supplied   by   the   manufacturer   without   an 
automatic closing procedure. To enable the automatic closing 
function proceed as follows: use the SEL key to navigate to T. 
PAUSA when the respective LED is flashing, then press the 
SET key again briefly; the automatic closing time is stored and 
the T. PAUSA LED remains lit constantly. 
To restore the initial configuration (without automatic closing) 
navigate to T.PAUSA when the respective LED is flashing then 
press the SET key twice within 2 seconds; the LED switches off 
and the operation is complete.

When programming, you can use the radio control key on the  
control unit instead of the SET key, if stored previously.

8) T. RIT. ANTE:

  (Programming door delay of max. 15 sec.)

The control unit is supplied by the manufacturer without door 
delay   during   opening   and   closing.   To   programme   the   door 
delay time, follow this procedure with the shutter closed: with 
the SEL key to the RIT.ANTE LED when flashing, press the 
SET key, wait for the desired interval of time, then press the 
SET key again; the fixed door delay time of 2 seconds during 
opening is stored, the door delay time during closing is stored 
for   the   programmed   time   and   the   RIT.ANTE   LED   is   on.
To restore the initial configuration (without door delay) go to the 

RIT.ANTE LED when flashing  then press the SET key  twice 
within   2   seconds;   the   LED   goes   off   and   the   operation   is 
completed.

EXTENDED MENU  1 

    

The control unit is supplied by the manufacturer with only the 
option   of   directly   selecting   the   functions   listed   in   the   main 
menu.
To enable the functions listed in extended menu 1, proceed as 
follows:     press   the  SET  button   and   hold  for   5  seconds;   the 
T.PAUSA and RIT. ANTE LEDs will flash in alternation and you 
have 30 seconds to select the functions of Extended Menu 1 
using the SEL and SET buttons; after another 30 seconds, the 
control unit returns to the main menu.

----------------------    EXTENDED MENU 1    -----------------

Led reference           Led off                        Led on

A) TIPO MOTORE    INB. CMD AP = OFF         INB. CMD AP. = ON 

B) AUTO PGM          Electronic brake = ON   Electronic brake = OFF
C) CODE                 Automatic                       Step-by-step

D) CODE PED.        Aries effect = OFF         Aries effect = ON  
E) T. MOT.              Closure effect = OFF      Closure effect = ON    

F) T.MOT.PED.       Follow Me = OFF           Follow Me = ON    

G) T. PAUSA            Flashing beacon ON/OFF in alternation 
H) RIT. ANTE           Flashing beacon ON/OFF in alternation 

A) TYPE OF MOTOR 
(

command   inhibition  during   opening  and   pause   time,   if 

entered

) :

The   command   inhibition   function   during   opening   and   pause 
time,   if   entered,   is   used   when   automation   includes   the   loop 
detector.   During   opening  or  pause  the   control   unit  does   not 
detect   the   commands   given   by   the   loop   detector   at   every 
passage. 
The   control   unit   is   supplied   by   default   with   the   command 
inhibition function during opening and pause time not enabled. 
To  enable   the  function  follow  this   procedure:  check   that  the 
Extended   Menu   1   is   enabled   (the   T.PAUSA   and   RIT   ANTE 
LEDs start flashing in alternation), use the SEL key to navigate 
to TIPO MOTORE when the respective LED is flashing, and 
press the SET key: the TIPO MOTORE LED switches on and 
programming is complete.
Repeat the operation to restore the previous configuration.

B) AUTO PGM (Electronic brake) :

The   control   unit   is   supplied   by   the   manufacturer   with   the 
electronic   brake   function   disabled.   To   enable   the   function 
proceed as follows: check that the extended menu 1 is enabled 
(the   T.   PAUSA   and   RIT   ANTE  LEDs   start   flashing   in 
alternation), use the SEL key to navigate to AUTO PGM when 
the corresponding LED is flashing and press the SET key: the 
AUTO PGM LED switches on and programming is complete. 
The control unit reduces the forward motion of the gate due to 
inertia in the presence of a stop or inversion command. Repeat 
the operation to restore the previous configuration.

C) CODE (Automatic/Step-by-step operation):

The   control   unit   has,   by   default,   the   operating   logic   for 
“automatic” operation. To select the operating logic for “step-
by-step”   operation,   proceed   as   follows:  check   that   the 
Extended   Menu   1   is   enabled   (the   T.PAUSE   and   RIT   ANTE 
LEDs  start flashing in alternation), press the SEL key until the 
CODE Led flashes, then press the SET key; the CODE Led 
turns   on  and   remains  steady   and  programming   is  complete. 
Repeat the operation to restore the previous configuration.

D) CODE PED. (Aries (ramming) effect) :

The control unit is supplied by the manufacturer with the aries 
(ramming)   effect   function   disabled.   To   enable   the   Aries 
(ramming) effect at maximum power, proceed as follows: check 
the extended menu 1 is enabled (the T.PAUSA and RIT ANTE 
LEDs flash in alternation),  press the SEL key until the CODE 
PED Led flashes, then press the SET key, at the same time the 
CODE   PED   LED   turns   on   and   remains   steady   and 

                                                                                            3                                                      Rev. 1.0    08/10/2010

Содержание LRS 2239

Страница 1: ...ommand impulse is received before the activation of the limit switch the direction of movement of the mechanism will be reversed whether engaged in opening or closing operations Step by step Using either the radio control CODE led lit or the low tension button panel PUL to operate the gates commands will have the following effect the first command impulse activates the opening mechanism either for...

Страница 2: ... key selects the type of function to be stored selection is indicated by a flashing LED By pressing the key repeatedly you can select the desired function The selection remains active for 10 seconds indicated by the flashing LED after 10 seconds the control unit returns to its original status SET key programmes the information according to the type of function selected previously using the SEL key...

Страница 3: ... key to the RIT ANTE LED when flashing press the SET key wait for the desired interval of time then press the SET key again the fixed door delay time of 2 seconds during opening is stored the door delay time during closing is stored for the programmed time and the RIT ANTE LED is on To restore the initial configuration without door delay go to the RIT ANTE LED when flashing then press the SET key ...

Страница 4: ...f the transmission code not enabled to enable the function proceed as follows check the extended menu 2 is enabled the T PAUSA and RIT ANTE LEDs flash simultaneously press the SEL button until the TIPO MOTOR LED flashes then press the SET key at the same time the LED TIPO MOTOR turns on and remains steady and programming is complete Repeat the operation to restore the previous configuration B AUTO...

Страница 5: ... the TIPO MOTORE AUTO PGM and CODE LEDs are steady while the CODE PED Led flashes press SET to confirm The default setting is Level 3 RESET To restore the default configuration press the SEL and SET keys simultaneously all RED LEDs will light up and then switch off DIAGNOSTICS Photocell test The control unit can be fitted with safety devices in accordance with step 5 1 1 6 of the EN 12453 standard...

Страница 6: ...back of the casing is set up for mounting on a wall holes for mounting with nogs or holes for screws Take all precautions to ensure the IP degree of protection is not affected during installation If applicable the keypad for manual control must be mounted in such a way as not to compromise the safety of the user The motor reducer used to move the shutter must comply with section 5 2 7 of EN 12453 ...

Страница 7: ...7 Rev 1 0 08 10 2010 ...

Отзывы: