background image

4.  ASSEMBLY

4.1.    

Remove compressor from packaging and inspect for any shortages or damage. If anything is found to be missing or damaged contact  

 

your Sealey stockist.

4.2.    

Save the packing material for future transportation of the compressor. We recommend that you store the packing in a safe location, at  

 

least for the period of the guarantee. Then, if necessary, it will be easier to send the compressor to the service centre.

4.3.    

Confirm that the mains voltage corresponds with the voltage  shown on the compressor data plate.

4.4. 

  

Position the compressor on a flat surface or with a maximum 

permissible inclination of 10

0

. Site in a well ventilated place, protected  

 

against atmospheric pollution and not in a place subject to explosion hazard. If the surface is inclined and smooth, check if the  

 

 

compressor moves while in operation. If the surface is inclined make sure it cannot fall, securing it in a suitable way.

4.5. 

  

To ensure good ventilation and efficient cooling, the compressor’s belt guard must be at least 100cm from any wall (fig.2).

 

 

Compressors fitted on the tank, with fixed feet, should not be rigidly secured to the ground. In this case, we advise you to fit 4 

 

 

anti-vibration supports. Fit the 4 anti-vibration supports, raise the compressor using a suitable pallet truck or fork lift and push the 

 

 

supports onto the base of each foot (fig.3).

4.6.    

Take care to transport the compressor correctly, 

DO NOT

 overturn it or lift it with hooks or ropes.

4.7.    

Remove the plastic transit plug from the oil filler hole (fig.4A) and replace it with the filler/breather plug as shown in fig.4B. It is a

 

push fit, ensure that it is pushed fully home.

4.8.    

Before using the compressor, check the oil level by observing the sight glass as shown in fig.5. If the oil is not up to the max mark    

 

it should be topped up with synthetic oil suitable for temperatures ranging from -5°C to 45°C (viscosity 5W50). We 

DO NOT

 recommend  

 

using mineral oil in these compressors. 

DO NOT

 overfill.

 

NOTE:

 To gain access to the pump and motor you must remove the 4 bolts from the top lid of the sound proof casing. For  

 

 

some servicing such as draining oil, you must also remove the rear panel by removing the 4 bolts. 

 

  

 

5.  OPERATION

 

‰

   WARNING! 

Ensure that you have read, understood and apply Section 1 safety instructions.

 

‰

   IMPORTANT! 

The use of extension leads to connect this compressor to the mains supply is not recommended as the resulting voltage  

  drop reduces motor, and therefore pump performance and could cause damage to your compressor.

 NOTE:

 Take care when selecting tools for use with the compressor. Air tool manufacturers normally express the volume of air required  

 

to operate a tool in cubic feet per minute (cfm). This refers to free air delivered by the compressor (‘air out’) which varies according  

 

to the pressure setting. 

DO NOT

 confuse this with the compressor displacement which is the air taken in by the compressor (‘air in’).  

 

‘Air out’ is always less than ‘air in’ due to losses within the compressor.

5.1.    

STARTING THE COMPRESSOR

5.1.1.   

To turn the compressor on, plug mains lead into mains supply, 

press the “ON” button on the front panel See fig.6.

 

5.1.2.   

When starting the compressor for the first time, leave it running with no air tools connected to the air outlet. Make sure that 

 

pressure in the tank rises and that the compressor stops automatically when the maximum pressure value allowed (written on the    

 

plate and shown on the gauge in fig.6) is achieved. The compressor will now operate automatically. The pressure switch stops the motor  

 

when the maximum tank pressure is reached and restarts it when the pressure falls below the minimum threshold - approx. 2bar (29psi)  

 

less than the maximum pressure.

5.1.3.   

Stop the compressor by pressing the “OFF/RESET” button in fig.6. The compressed air inside the compressor head will flow out, making  

fig.2

fig.4

Oil Drain

fig.5

SAC2203BLN.V2       Issue 2 (H, 3, F) 09/07/18

Original Language Version

© Jack Sealey Limited

fig.3

Содержание SAC2203BLN.V2

Страница 1: ...ny doubt about electrical safety contact a qualified electrician 1 1 3 Ensure that the insulation on all cables and on the appliance is safe before connecting it to the power supply See 1 1 1 and use a Portable Appliance Tester 1 1 4 Ensure that cables are always protected against short circuit and overload 1 1 5 Regularly inspect power supply cables and plugs for wear or damage and check all conn...

Страница 2: ...lter the tank in any way and DO NOT strap or weld anything to the tank 8 8 DO NOT subject the tank to impact vibration or to heat and DO NOT allow contact with abrasives or corrosives 9 9 Drain condensation from tank daily and inspect inside walls for corrosion every three months and have a detailed tank inspection carried out annually The tank shell must not fall below the certified thickness at ...

Страница 3: ... C to 45 C viscosity 5W50 We DO NOT recommend using mineral oil in these compressors DO NOT overfill NOTE To gain access to the pump and motor you must remove the 4 bolts from the top lid of the sound proof casing For some servicing such as draining oil you must also remove the rear panel by removing the 4 bolts 5 OPERATION WARNING Ensure that you have read understood and apply Section 1 safety in...

Страница 4: ...ocated under the tank fig 8 Place a container under the valve and open the valve by turning anti clockwise WARNING Take care if there is still pressure inside the cylinder as water could flow out with considerable force Recommended pressure 1 2bar max b Check oil level and if necessary top up 6 1 3 OPERATIONS TO BE CARRIED OUT EVERY 50 100 HOURS or more frequently if the compressor operates in a v...

Страница 5: ...red for any claim fig 7 fig 8 fig 9 Fault Cause Remedy Pressure drop in the tank Air leaks at connections Run compressor to max pressure switch off Brush soap solution over connections and look for bubbles Tighten connections showing leaks If problem persists contact Authorised Service Agent Pressure switch valve leaks when compressor is idle Non return valve seal defective Discharge all tank pres...

Отзывы: