21
© Sealevel Systems, Inc. R91001 Manual | SL9211 11/2022
Open Collector Outputs
Directly control eight outputs via the Relio R9’s open-collector outputs found on the front of the enclosure.
The open collector outputs have a range of 5 – 30V with a maximum sink current of 500mA on a single
output with a combined maximum sink current of 580mA on all outputs.
Connector:
OPEN-COLLECTOR OUTPUTS
Manufacturer:
Weco
Part Number:
110-M-111/10
Description:
Terminal Block 10 position 3.5mm spacing
Mates with:
Weco 110-A-111/10 10 position screw-terminal plug (provided)