GSM-R5-DIN_User_Manual_EN_v1-11.docx
Strana 6 z 7
10.2
Comfortable temperature control
If you need regulate higher temperature than temperature set on thermoregulator. You can use different wiring, where you disable thermoregulator by output Y6.
Command 1234 Y6 OFF will enable thermoregulator A3 to regulate heater. Heater will heat until it reaches selected temperature. Those commands can be sent in one SMS message
simultaneously.
Regulation to 25°C
1234 Y6 OFF Y5 TEPL 25
( thermoregulator is disabled)
Regulation to 22°C 1234 Y6 ON Y5 OFF
( thermoregulator is set to 22°C)
Regulation to 7°C
1234 TEPL 7
( thermoregulator is disabled)
10.3
Digital inputs
Example of connection of inputs X1 and X2 as contact status detector:
If you need to monitor a potential free contacts (for example magnetic contacts of the alarm circuit or relay contacts), connect them
directly to inputs X1 and X2.
230VAC
PE
N
L
CIRCUIT
BREAKER
CONTACTOR
I
O
AUTO
I
O
SWITCHBOARD
L
N
PE
HEATING
ROOM
TEMP.
SENSOR
22°C
L
N PE
Switch ON
the heating
via room
thermoregulator
ROOM
THERMORE
GULATOR
ELECTRONIC
RIPPLE
CONTROL