SDC 101-DE Скачать руководство пользователя страница 11

P:\INSTALLATION INST\Delayed Egress\INST-101DE_KDE.vsd      Rev E               07-15     Page 10

SPECIFICATIONS

Inputs:
Voltage input:

Auto sensing 12/24 VDC

Reset input:

N/O, Dry

Rex input:

N/O, Dry

Trigger:   

N/C or N/O, Dry

IBO input

:

N/O, Dry

Monitoring Outputs:
Alarm Output:

1 Amp @ 30VDC SPDT, dry

Locked Output:

1 Amp @ 30VDC SPDT, dry

Mechanical Specifications:
Controller:

6.5" x 4.5" x 1.5"
(165 x 114 x 38mm)

1581DE:  

8.75" x 2.125" x 1.25"
(222 x 54 x 32mm)

1571DE/1511DE:

11" x 2.75" x 1.562"
(279 x 69.9 x 39.7mm)

1575DE/1576DE:

8.7" x 2.5" x 1.6"
(221 x 63.5 x 41mm)

MODELS

101-DE

1581DEV
1571DEV
1511DEV

101-KDE

1575DEU
1576DEU

DEC-J

101-DE, DEC-J, SHD-J

DELAYED EGRESS CONTROLLER

101-DE

Wall mount controller with keypad control and reset, 180mA @ 12/24 VDC.

101-KDE

Wall mount controller with both keypad and key switch control and reset (less cylinder).

MAGNETIC LOCK WITH INTEGRATED ACTIVATION SENSOR

Specify 2 for pair of doors.

1511DEV

Single, 1650 lbs. holding force, 670/350 mA @ 12/24 VDC, 628 std

1571DEV

Single, 1200 lbs. holding force Energey Saver, 250/125 mA @ 12/24 VDC, 628 std

1581DEV

Single, 650 lbs. holding force, 440/220 mA @ 12/24 VDC, 628 std

Outdoor Locks.

1575DEU

Single outdoor magnetic lock with bond sensor, 630

1576DEU

Single face drilled outdoor magnetic lock with bond sensor, 630

Lock Finish

Not available with outdoor lock
V

628 Clear Anodized Aluminum 

(Std)      

X

Dark Bronze Power Coat (313/613 equal)

Y

Black Anodized

Optional Outputs

B

Magnetic Bond sensor, indicates locked with full holding force, low holding force,

unlocked, tampering and obstructions (1581DEV SPST only).

Door position sensor, indicates door open and door closed.  Commonly used to

verify egress after alarm and exit delay activation.  Not available with 1581DE,
1576DE or 1575DE.

VI

Spanish, or English and Spanish, or English and French verbal announcement.

VIC 

Custom verbal announcement 

(minimum 10 piece purchase)

.

ACCESSORIES

MSB550

Mechanical REX Exit bar for activation of locks on doors without latch assemblies.

PSB560 

Sure Exit® REX sensor bar for activation of locks  on doors without latch assemblies

101-SP

External 15W speaker connects directly to 101-DE for enhanced decibels on site or 

remote voice message annunciation.

101-4AM

Four door station with LED’s and alarm tone for remote annunciation (indoor use).

TCC       

Desk top console for remote control and annunciation of 4 – 12 doors.

101-1AK

Outdoor reset/bypass key switch with LED and Audible annunciator.  2-gang outdoor 

box required.  (Interior 101-DE and 1575DE or 1576DE outdoor magnetic lock required).
(Cylinder not included).

DEC-J   

3-gang Interior surface mount box for 101-DE

1, 2 or 3 gang box mounted.

SHD-J   

Shroud for surface mount box DEC-J outdoor use

DEC-J required.

Only 101DE/KDE have been UL Listed as

Special Locking Arrangements to UL

standard 294 and NFPA 101.

PUSH UNTIL ALARM 

SOUNDS.  DOOR CAN BE 
OPENED IN 15 SECONDS.  

PUSH UNTIL ALARM 

SOUNDS.  DOOR CAN BE 
OPENED IN 15 SECONDS.  

TO FIRE COMMAND 
CENTER

115 VAC

Door Without Latch Assembly

Activation By Sure Exit   Push Bar

R

Power Supply

Power Transfer

Hinge or Loop

MSB550/PSB560

REX Bar

PUSH UNTIL ALARM 

SOUNDS.  DOOR CAN BE 

OPENED IN 15 SECONDS.  

Standard Exit 

Device

No switch

No Power Transfer

TO FIRE COMMAND 
CENTER

115 VAC

Door With Latch Assembly

Activation By Door Movement

Power 

Supply

Содержание 101-DE

Страница 1: ...OFF BYPASS BYPASS RESET 101 4AM GRN SECURE YEL ALARM RED UNLOCKED OFF BYPASS AUDIBLE SHUNT 101 PAM GRN SECURE YEL ALARM RED UNLOCKED OFF BYPASS AUDIBLE SHUNT ACCESS ON OFF GRN SECURE YEL ALARM RED UNL...

Страница 2: ...ST Delayed Egress INST 101DE_KDE vsd Rev E 07 15 Page 1 Any suggestions or comments to this instruction or product are welcome Please contact us through our website or email engineer sdcsecurity com A...

Страница 3: ...o re secure the door Unlocking the door for extended periods of time Authorized Bypass mode is accomplished by entering an Authorized Bypass code on the integral keypad momentarily turning the optiona...

Страница 4: ...ture assembly with tray required for proper operation of the trigger switch EMLock Door Mount magnet and armature tray assembly per template ARMATURE HOLDER ARMATURE 1 2 DOOR 1 1 4 SEX NUT 5 16 18 ARM...

Страница 5: ...d PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS RECESSED MOUNTING DRY WALL 3 3 4 PUSHUNTILALARMSOUNDS DOORCANBEOPENEDIN15 SECONDS KEY CYLINDER INSTALLATION KDE Model Only 1 Cut hole in dry wall to...

Страница 6: ...E WALL or POST MOUNTING with WEATHER SHROUD 1 Use optional 3 Gang Box inside optional Shroud as a template to drill pilot holes through shroud and into post or wall 2 Mount 3 Gang Box and Shroud to Po...

Страница 7: ...PACKING FOAM BETWEEN WALL AND UNIT TO PREVENT DAMAGE TO FACEPLATE USE 1 1 4 SCREWS SUPPLIED WITH WALL MOUNT FRAME TO HANG UNIT TEMPORARILY FOR WIRING PURPOSES VIEW A A WIRE UNIT AS SHOWN SHOWN WITH NO...

Страница 8: ...7 8 3 4 5 6 7 8 l PAIR OF DOORS 101 DE 101 KDE PWR LOCK RED R NO C TRIG REX RESET C NO C NO C NO To Power Supply WARNING CONTACT THE AUTHORITY HAVING JURISDICTION FOR APPROVAL PRIOR TO SELECTING DELAY...

Страница 9: ...lay is counting down with audible alarm voice instructions Once the display reaches 00 the door will unlock 15 14 01 DELAYED EGRESS MODE 00 00 The door is unlocked and has been opened ALARMED UNLOCKED...

Страница 10: ...ess Changing the Master Code User 1 is always used as the Master Code and is required to access keypad programming The Factory Default Master Code is 1234 It is strongly recommended that a new Master...

Страница 11: ...ctions 1581DEV SPST only D Door position sensor indicates door open and door closed Commonly used to verify egress after alarm and exit delay activation Not available with 1581DE 1576DE or 1575DE VI S...

Страница 12: ...ystem 6 Upon power up you must manually reset the lock to activate the IBO input P INSTALLATION INST Delayed Egress INST 101DE_KDE vsd Rev E 07 15 Page 11 Connection to a Infant Patient Monitoring Sys...

Страница 13: ...R Power Supply Power Transfer Hinge or Loop MSB550 PSB560 REX Bar Lock Power RED LED GRN LED LED COM 101 1A or 101 1AK REMOTE ANNUCIATION REMOTE TRIGGER MSB550 PSB560 REX TRIG RESET IBO J4 J6 J1 KEYPA...

Страница 14: ...SECURE YEL ALARM RED UNLOCKED OFF BYPASS BYPASS RESET 101 4AM GRN SECURE YEL ALARM RED UNLOCKED OFF BYPASS AUDIBLE SHUNT 101 PAM GRN SECURE YEL ALARM RED UNLOCKED OFF BYPASS AUDIBLE SHUNT ACCESS ON OF...

Отзывы: