SimpleComTools, LLC
XML1000 – User Manual
SimpleComTools, LLC
31
AnMXSP
Description:
Analog Input Maximum Setpoint.
The HIGH setpoint for exception reporting.
Query
AT*AnMXSP
Query the MINIMUM (LOW) SETPOINT of the analog input.
Response value will be in either VOLTAGE or DECIMAL format, whichever one
is selected in the AUNITS register.
Options:
n = (1 – 8)
Response value is contingent upon the status of the AUNITS register.
(0.00 – 5.00) for units with 0-5VDC inputs when AUNITS=0
(0.00 – 30.00) for units with 0-30VDC inputs when AUNITS=0
(0.00 – 20.00) for units with 4-20mA inputs when AUNITS=0
(0 – 1023) when AUNITS=1
Configuration
AT*AnMNSP=y
Command to set the MAXIMUM (HIGH) SETPOINT for the analog input.
New value must be in the same format selected in the AUNITS register.
Options:
n = (1 – 8)
y = (0.00 – 5.00) for units with 0-5VDC inputs when AUNITS=0
y = (0.00 – 30.00) for units with 0-30VDC inputs when AUNITS=0
y = (4.00 – 20.00) for units with 4-20mA inputs when AUNITS=0
y = (0 – 1023) when AUNITS=1
Digital Inputs (States)
AT Command
Description
Tn
Description:
Digital Input TYPE. Adjusts the value of the input between
Normally Open and Normally Closed.
Query
AT*Tn
Query the state of a Digital Input.
Options:
n = (1 - 8)
Configuration
AT*Tn=y
Options:
n = (1 – 8)
y = (0 or 1)
y = 0 (Normally Open)
y = 1 (Normally Closed)
Dn
Description:
Current state of the Digital Input. Response value will indicate the
state of the switch displayed as a 0 or 1.
Query
AT*Dn
Query the state of a Digital Input.
Options:
n = (1 – 8)