ELECTRICAL SEQUENCE

Refer the wiring diagram as needed.

The "Power" light on the board glows whenever
there is power to the machine (and the master
switch is ON).

If the machine is switched off at the master switch,
but is otherwise ready to go, switching the master
switch to ON does the following:

••

The bin empty and power lights on the circuit
board glow.

••

There is a 15 second delay

••

If there is enough water in the reservoir, the
circuit board will allow the machine to start up.

Start up consists of:

••

The compressor contactor coil receives power
from the circuit board.

••

The contactor is energized, connecting power
to the compressor, and the compressor starts.

••

The auger motor receives power from the circuit
board and starts.

••

As ice goes past the ice level sensors, the bin
empty light will stay on and  the machine will
continue to run, unless the ice stays between
the sensors for more than 15 seconds (bin full).
At that point, the bin empty light goes out, and
the machine shuts down.

Other reasons for shut down:

••

Low water level (as sensed by the thermistor in
the reservoir).

••

Excessive auger motor amp draw, measured by
the circuit board.

••

If the auger motor amp draw becomes
excessive twice in an hour, the auger motor is
shut down and the circuit board must be
manually reset. If this condition occurs it means
that the drive train is in need of cleaning.
maintenance or repair.

Shut Down consists of:

••

The compressor contactor opens

••

The compressor stops

••

The auger motor is run by the circuit board for 2
more minutes, clearing out ice in the
evaporator, and then

••

The auger motor no longer receives power from
the circuit board, and the auger motor stops.

After a 6 minute delay, If the ice level sensor is
clear (bin empty) for more than 15 seconds, the
machine will start up again.

Another purpose of the circuit board is to turn the
machine off if there is not enough water in the
machine.

••

When the water level  in the reservoir falls
below the tip of the water level sensor, the
machine will "shut down"

••

After a 6 minute delay, if the water refills the
reservoir, the machine will start up again.

Separate from the circuit board:

••

If the high pressure control (cut out switch)
opens,  the compressor will stop immediately
(through the contactor ). It must be manually
reset.

••

The master switch is the manual control for the
complete machine, but it is not a service
disconnect.

Ice Vending

••

When a user places a container in front of the
Touch Free ice sensor and below the ice
delivery chute, the circuit board connects power
to the bin drive motor and ice is dispensed for
as long as the container is present.  If the user
does not remove the container, ice will be
dispensed for 60 seconds and then stop.

••

When a user places a container in front of the
Touch Free water sensor, and below the water
spout, the circuit board connects power to the
water solenoid valve and water is dispensed. If
the user does not remove the container water
will be dispensed for 90 seconds and then stop.

Splash panel cleaning:

••

A switch, located next to the water spout, may
be pushed to disable the Touch-Free sensors
for splash panel cleaning. It automatically
resets after 2 minutes, or, if pushed within the 2
minutes, resets the circuit board to enable the
Touch Free sensors.

Splash Panel

Cleaning or

Touch Free

Disable Switch

 

TDE550 & TDE650

August 1994

Page 13

Содержание TDE550

Страница 1: ...s Page 3 FOR THE INSTALLER Wall Mount Kit Page 5 FOR THE PLUMBER Page 6 FOR THE ELECTRICIAN Page 7 FOR THE INSTALLER Final Check List Page 8 INITIAL START UP Page 9 COMPONENT DESCRIPTION Page 10 COMPO...

Страница 2: ...WE 6A 48 5 x 26 x 22 5 same same same 41 x 26 x 22 5 same same same NUGGET same same same same same same same Air Water Air Water Air Water Air Water 115 60 1 115 60 1 230 50 1 230 50 1 115 60 1 115 6...

Страница 3: ...ng plant it takes a raw material water and turns it into a food product ice The purity of the water is very important in obtaining pure ice and in maximizing product life This section is not intended...

Страница 4: ...echanical hoist is recommended to lift it to the height required to install it The DMS machine stand has holes in the top that match up with threaded holes in the icemaker dispenser Place the cabinet...

Страница 5: ...either side through the pre punched holes using standard plumbing practices Interior plumbing lines must be disconnected from the original connections and plugged when routing through the side or bas...

Страница 6: ...a 3 8 FPT condenser inlet at the back of the cabinet The water pressure to all lines must always be above 20 psig and below 80 psig Drains Air Cooled Models There is one 3 4 FPT drain at the back of...

Страница 7: ...achine requires a solid chassis to earth ground wire The ice maker should be connected to its own electrical circuit so it would be individually fused Voltage variation must remain within design limit...

Страница 8: ...3 Have all of the plumbing connections been made and checked for leaks 4 Has the machine been leveled 5 Is there a minimum of 6 inches of clearance at the left and right sides of an air cooled machine...

Страница 9: ...it should be 38 PSIG or 2 PSIG The air cooled discharge pressure will depend upon air and water temperatures but should be between 240 PSIG and 340 PSIG Water cooled discharge pressure should be abou...

Страница 10: ...enses the presence of ice in the bottom of the ice discharge chute Operates to turn the ice machine on and off automatically as the level of ice in the bin changes Drain Tube When uncapped and lowered...

Страница 11: ...where the two seal faces meet Ice Sweep A plastic cap with fingers It revolves with the auger to sweep the ice into the ice chute Breaker Where the ice is compressed and much of the extra water is sq...

Страница 12: ...r Fan motor Bin drive motor Auger drive motor Water solenoid In addition a Clean switch is available to temporarily disable the Touch Free sensors for cleaning of the splash panel On Off Switch Manual...

Страница 13: ...auger motor no longer receives power from the circuit board and the auger motor stops After a 6 minute delay If the ice level sensor is clear bin empty for more than 15 seconds the machine will start...

Страница 14: ...es to the water regulating valve then to the water cooled condenser and down the drain There is also an additional water circuit to an electric valve When the Touch Free system senses a container for...

Страница 15: ...rigerant depending upon the temperature of the evaporator warmer evaporators get more refrigerant and colder evaporators get less At the evaporator the refrigerant enters an area of relatively low pre...

Страница 16: ...scharge out this chute as long as the vane is turning It stops when the dispensing vane stops If the container is in front of the Touch Free sensor on the right side the inlet water valve will open an...

Страница 17: ...th sanitizer 4 The splash panel requires special attention to clean it Push and release the Splash Panel Cleaning switch located to the left of the water spout This disables the Touch Free sensors so...

Страница 18: ...grees F 8 Slowly pour the cleaning solution into the water reservoir until it is full Wait 15 minutes then switch the master switch to ON 9 As the ice maker begins to use water from the reservoir cont...

Страница 19: ...sensors from the grommets in the ice chute and wipe them clean 4 The bearing in the breaker should also be checked at least two times per year A Check the bearing by removing the ice chute cover unscr...

Страница 20: ...water treatment For more information on removal of these parts see REMOVAL AND REPLACEMENT 1 To remove the auger remove the front and top panels 2 Push bail clamp off of cover and remove cover 3 Unscr...

Страница 21: ...e cannot keep up with needs Check for jam up of ice in dispense chute Pull chute down and allow ice to fall out Return chute to its normal place If there is ice check that the bin vane rotates if not...

Страница 22: ...l sensor not shutting unit off when there is lack of water Will not dispense ice Vane turns ice is available but will not flow out of bin Check position of bin bottom It must have its slot over the ic...

Страница 23: ...ce Normal 6 minute off delay start To prevent short cycling the machine will not restart after any shut off excpet power to the board until 6 minutes have passed 5 Off Timer ON Unit cycling off Too mu...

Страница 24: ...reservoir 7 Remove mounting screws from reservoir bracket and remove reservoir from icemaker 8 Reverse to reassemble BIN CONTROLS Ice Level Sensors 1 Disconnect electrical power 2 Remove front panel...

Страница 25: ...he bearing Check for rust rough spots and damage a The bearing is pressed into the breaker to remove the bearing and replace it an arbor press is needed b Replace lower seals before installing new bea...

Страница 26: ...ad cap screws holding breaker to evaporator d Lift up remove breaker from evaporator e If the auger is stuck use a slide hammer type puller to pull on the auger at the threaded hole The size of that h...

Страница 27: ...or the snap ring 2 Replace the snap ring and pull the water seal down against it 3 The part of the water seal that rotates with the auger must also be replaced Remove the old part from the auger and c...

Страница 28: ...tor has been inspected fasten the evaporator to the gear motor be sure that the number of shims indicated on the gear case cover is in place between the gearcase cover and the drip pan gasket Torque t...

Страница 29: ...kely to be fine if the oil is If there is evidence of water in the oil rusty bearings and gears the oil having a creamy white appearance oil level too high carefully inspect the bearings and gears If...

Страница 30: ...ipment is required to locate small refrigerant leaks Usually a leak detector capable of detecting a Halogenated refrigerant or HFC 134A will work Check with the leak detector manufacturer if in doubt...

Страница 31: ...red This system has a critical charge it must be recharged with the correct amount of refrigerant as listed on the nameplate of the ice machine or performance will suffer Anytime the refrigeration sys...

Страница 32: ...itch off the vacuum pump 2 Place a drum of R 404A onto an electronic scale 3 Attach the charging hose to the drum 4 Open the valve on the drum and purge the charging hose 5 Zero out the scale 6 Shut t...

Отзывы: