OPERATION: Refrigeration
LOW CONDENSING TEMPERATURE
The refrigeration system under low condenser air
temperatures is much the same as it is under
higher temperatures, with the exception that the
resulting low head pressures cause the head
pressure control to close off the liquid line between
the condenser and the receiver.
This forces more refrigerant into the condenser
(with a small amount of discharge gas going into
the receiver to maintain pressure until the head
pressure is built back up to 180 psig). At that
pressure the valve opens up the liquid line from
the condenser to the receiver.
LIQUID LINE
DISCHARGE
LINE
HEAD
PRESSURE
CONTROL
VALVE
RECEIVER
COMPRESSOR
LIQUID LINE
VALVE
DETAIL OF HEAD
PRESSURE CONTROL
VALVE
EVAPORATOR
THERMOSTATIC
EXPANSION
VALVE
REMOTE CONDENSER
NME1250R
August 1993
Page 17