background image

Page 18

Page 18

The thermostat sensing bulb is located into a
plastic tube (bulb holder) secured by two clips
directly to the evaporator serpentine.
This control determines the length of the freezing
cycle and correspondingly the size of the cubes.
A lower setting will produce a larger cube
(oversize) while a higher setting a smaller cuber
(shallow size).
When closed on contacts 3-2 it activates the
defrost or harvest cycle components.
The cube size control is set up in the factory
(knob in the black dot position) and doesn't
require any adjustment when the ambient
temperature remains between 15 and 30

°

C

(60 and 90

°

F).

F.

FAN MOTOR (Air cooled version)

The fan motor is electrically connected in parallel
to the water pump and it operates continuously
only during the freezing cycle keeping the proper
head pressure by circulating air through the
condenser fins.

G.

COMPRESSOR

The hermetic compressor is the heart of the
refrigerant system and it is used to circulate and
retrieve the refrigerant throughout the entire
system. It compresses the low pressure
refrigerant vapor causing its temperature to rise
and become high pressure hot vapor (hot gas)
which is then released through the discharge
valve.

H.

WATER SPRAY SYSTEM

Through its nozzles it sprays the water in each
individual cup to be frozen into ice.

I.

CLEANING SWITCH

Located on the bottom side of the control box is
used to energize the water inlet and the hot gas
valves so to charge the water into the sump of the
machine when neaded.

J.

HI PRESSURE CONTROL (Water cooled
version)

Used only on the water cooled versions it operates
to keep between 8.5 and 10 bars (120 

÷

 140 psig)

the hi-side or discharge pressure of the refrigerant
system by energizing the coil of the water inlet
solenoid valve that control the cooling water flow
to the condenser.

K.

GREEN MASTER SWITCH PUSH BUTTON

Located in the front of the machine it’s used to
switch ON and OFF the unit by pushing its green
push button. When ON, its green light is ON as well.

L.

RED ALARM/RE-SET PUSH BUTTON

Located in the front of the machine (just beside
the Master Switch) it works in conjuction with

the Cleaning Remind Board and it’s activated
when:
• Consensing temperature is higher then 70

°

C

(air cooled version) - ON steady with machine
in OFF mode

• Condensing temperature is higher then 60

°

C

(water cooled version) - ON steady with
machine in OFF mode

• Condenser sensor out of order - Blinking

twice and repeat with machine in OFF mode

• Condenser air filter need to be cleaned - ON

steady with machine in ON mode

• Water system need to be cleaned - Slow

blinking with machine in ON mode.

On the first two cases it’s possible to Re-Set the
operation of the machine pushing and hold the
Red Alarm Re-Set Button by 5" till the Red Light
is OFF.
On the third case, it’s necessary first to replace
the condenser sensor then, push and hold for 5"
the Red Re-Set Button.

M. CLEANING REMIND AND PWD PC BOARD

Located on the front left side of the machine, it
works in conjuction with the condenser sensor
and the Red Alarm Re-Set Push Button.

It is used to energise the Water Drain Pump any
time the level of the water into the Sealed water
Reservoir reaches the upper metal pins (low
power electrical circuit closed through the water).
The water pump is kept energised by the PWD
PC Board for 8 seconds.

It consists of a Printed Circuit Board with a step
down transformer (230V - 12V), a relay, a Dip
Switch with two keys, a Jumper for the set up of
the Cut OFF/Alarm condensing temperature
(70

°

C - jumper OUT - for air cooled version and

60

°

C - jumper IN - for water cooled version), a

green four contacts connector for power IN and
OUT, a Red socket for the Water Level Sensor,
a Black socket for the Condenser Sensor and a
White socket for the Red Alarm Re-Set Push
Button.

The main function of this PC Board is to switch
OFF the machine when the condensing tempe-
rature is higher of its setting value or signal out
the need for the cleaning of the condenser air
filter (air cooled only) or of the water system.

WATER LEVEL

SENSOR

CONDENSER

SENSOR

RESET

BUTTON

CONNECTOR

DIP SWITCH FOR CLEANING

REMIND SETTING

POWER IN & OUT
CONNECTOR

TRANSFORMER

JUMPER FOR 70

°

C - OUT - OR 60

°

C

-IN - CONDENSING TEMPERATURE

Содержание EC 46

Страница 1: ... Italy Tel 39 02 93960 1 Aut Sel Telefax 39 02 93550500 Direct Line to Service Parts Phone 39 02 93960350 Fax 39 02 93540449 Website www scotsman ice com E Mail scotsman europe frimont it ISO 9001 Cert n 0080 SERVICE MANUAL EC 46 EC 56 EC 86 Cubers with storage MS 1000 94 REV 10 2008 ...

Страница 2: ...ons Water supply and drain connections Final check list Installation practice OPERATING INSTRUCTIONS Start up Operational checks OPERATING PRINCIPLES How it works Freezing cycle Harvest cycle Electrical sequence Components description ADJUSTMENT REMOVAL AND REPLACEMENT PROCEDURES Adjustment of the cube size Wiring diagram Service diagnosis MAINTENANCE AND CLEANING INSTRUCTIONS General Icemaker Cle...

Страница 3: ...directly related to the condenser air inlet temperature water temperature conditions of the condenser air filter and age of the machine To keep your SCOTSMAN CUBER at peak performance levels periodic maintenance checks must be carried out as indicated on Maintenance and Cleaning section of this manual MAX 40 C 35 C 5 bar 10 ice making capacity 25 24 23 22 21 20 19 18 17 16 Kg 32 27 21 15 10 AIR CO...

Страница 4: ...CIFICATIONS Basic electr Amps Watts Nr of wires Amps fuse 230 50 1 2 1 12 400 3 x 1 5 mm2 10 8 6 EC 46 CUBER machine specifications Cubes per harvest 18 medium A 15 C water temperature Dimensions HEIGHT 645 mm WIDTH 386 mm DEPTH 600 mm WEIGHT 42 Kgs 77 350 Bin Water req Capacity lt 24 HR EC 46 AS 6 Air EC 46 WS 6 Water ...

Страница 5: ...than 32 C The daily ice making capacity is directly related to the condenser air inlet temperature water temperature conditions of the condenser air filter and age of the machine To keep your SCOTSMAN CUBER at peak performance levels periodic maintenance checks must be carried out as indicated on Maintenance and Cleaning section of this manual 32 30 28 26 24 22 20 18 Kg 32 27 21 15 10 AIR COOLED M...

Страница 6: ...IFICATIONS Basic electr Amps Watts Nr of wires Amps fuse 230 50 1 2 1 12 400 3 x 1 5 mm2 10 0 90 270 EC 56 CUBER machine specifications Cubes per harvest 24 medium A 15 C water temperature Dimensions HEIGHT 695 mm WIDTH 386 mm DEPTH 600 mm WEIGHT 45 Kgs 7 6 7 Bin Water req Capacity lt 24 HR EC 56 AS 6 Air EC 56 WS 6 Water ...

Страница 7: ...he daily ice making capacity is directly related to the condenser air inlet temperature water temperature conditions of the condenser air filter and age of the machine To keep your SCOTSMAN CUBER at peak performance levels periodic maintenance checks must be carried out as indicated on Maintenance and Cleaning section of this manual 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24 Kg 32 27 21 15 10 AI...

Страница 8: ...ctr Amps Watts Nr of wires Amps fuse 230 50 1 3 3 18 480 3 x 1 5 mm2 10 0143 500 EC 86 CUBER machine specifications Cubes per harvest 24 medium A 15 C water temperature Dimensions HEIGHT without legs 795 mm HEIGHT with legs 915 mm WIDTH 530 mm DEPTH 600 mm WEIGHT 45 Kgs 8 9 8 4 Bin Water req Capacity lt 24 HR EC 86 AS 6 Air EC 86 WS 6 Water ...

Страница 9: ...ght and front to rear directions D ELECTRICAL CONNECTIONS See data plate for current requirements to determine wire size to be used for electrical connections All SCOTSMAN icemakers require a solid earth wire A INTRODUCTION This manual provides the specifications and the step by stepproceduresfortheinstallation start up and operation maintenance and cleaning for the SCOTSMAN EC series icemakers Th...

Страница 10: ...g the flexible tube supplied tothecoldwatersupplylinewithregularplumbing fitting and a shut off valve installed in an accessible position between the water supply line and the unit If water contains a high level of impurities it is advisable to consider the use an appropriate water filter or conditioner Water Cooled Versions On WaterCooledversionthewaterinletsolenoid valve has two separate outlets...

Страница 11: ...er supply pressure been checked to ensure a water pressure of at least 1 bar 14 psi 7 Check all refrigerant lines and conduit lines to guard against vibrations and possible failure 8 Havetheboltsholdingthecompressordown been checked to ensure that the compressor is snugly fitted onto the mounting pads 9 Have the bin liner and cabinet been wiped clean 10 Has the owner user been given the User Manua...

Страница 12: ...evaporatortemperaturereaches a preset value the evaporator thermostat or cube size control changes its contacts the freezing cycleendsandstartsthedefrostorharvestcycle Freezing time will range between 20 and 22 minutes in a 21 C ambient temperature Longer time for temperature above shorter when below Average complete cycle range is about 23 to 25 minutes I Check during the first defrost harvest cy...

Страница 13: ...Page 13 Page 13 Page 13 ...

Страница 14: ...Page 14 Page 14 ...

Страница 15: ...reaches the maximum level the two metal pins close the electrical contact through the water transmitting a low voltage current to the PC Board The PC Board activates the Water Drain Pump for 8 seconds pumping out most of PWD SYSTEM the water contained into the Sealed Water Reservoir The water can be pumped out up to 1 5 m rise or to 30 m on horizontal length POWER WATER INLET WATER DRAIN HAND DISC...

Страница 16: ...drain hose prevents the coming back of the discharged water SCHEMATIC SYSTEM Storage bin Overflow drain tube Storage bin drain tube Water tank inlet fitting Sealed water tank Water pump Check valve Vented tube Water level sensors Drain out Drain fitting ...

Страница 17: ...ox behind the front louvered panel The thermostat sensing tube is located into a bulb holder on the side wall of the ice storage bin where it automatically shuts the icemaker OFF when in contact with the ice and re starts the icemaker when the ice is removed Factory settings are 1 C 35 F OUT and 4 C 39 F IN E CUBE SIZE CONTROL EVAPORATOR THERMOSTAT The cube size control evaporator thermostat body ...

Страница 18: ... RE SET PUSH BUTTON Located in the front of the machine just beside the Master Switch it works in conjuction with the Cleaning Remind Board and it s activated when Consensing temperature is higher then 70 C aircooledversion ONsteadywithmachine in OFF mode Condensing temperature is higher then 60 C water cooled version ON steady with machine in OFF mode Condenser sensor out of order Blinking twice ...

Страница 19: ... Storage bin On its top cover are secured two metal pins Water Level Sensor connected to the PWD PC Board O WATER DRAIN PUMP Placed beside the Sealed Water Reservoir is used to pump out the water contained into the tank It is energised by the PWD PC Board for just few seconds P CHECK VALVE Placed on the discharge hose of the water pump it prevents the coming back of the pumped out water Q CONDENSE...

Страница 20: ...Page 20 Page 20 ...

Страница 21: ...Page 21 Page 21 WIRING DIAGRAM EC 46 EC 56 AIR AND WATER COOLED 230 50 60 1 The unit is shown on freezing cycle ...

Страница 22: ...Page 22 Page 22 WIRING DIAGRAM EC 86 AIR AND WATER COOLED 230 50 1 The unit is shown on freezing cycle ...

Страница 23: ...Page 23 Page 23 WIRING DIAGRAM EC 86 AIR AND WATER COOLED 230 60 1 The unit is shown on freezing cycle ...

Страница 24: ... the building If low contact the power company Non condensable gas in system Purge the system Dirty condenser Clean with vacuun cleaner air or stiff brush DO NOT use wire brush Air circulation blocked Allow sufficient air space all around unit Compressor starting device with Check for loose wires in starting loose wires device Cubes too small Cube size control set improperly Check and adjust for p...

Страница 25: ... pressure Clogged air filter Clean or replace Poor harvest Restriction in incoming water line Check water valve strainer and flow control If necessary enlarge the flow control orifice Too short defrost time Check temperature control Replace if necessary Cube size control set for too large Re set cube size control cubes Water inlet valve not opening Valve coil with open winding Replace valve Hot ga...

Страница 26: ... the sensing bulb inside the tube will warm up and cause the icemaker to restart This control is factory set and should not be reset until testing is performed 6 Check for refrigerant leaks NOTE The new EC series in the air cooled version are standard equipped with an air condenser filter as well as a Cleaning Reminder Board to remind to the end user the need for the cleaning of the air filter or ...

Страница 27: ... 11 SwitchONagainthemachineatfront master button switch to start the icemaking process Allow the ice maker to operate for about 20 minutes Then turn the cleaning switch to the cleaning position II till the release of the ice cubes from their cups NOTE The amount of Cleaner and the time needed for the cleaning of water system depends of the water conditions 12 Switch OFF the ice maker at master but...

Страница 28: ...e switch in cleaning position II switch it ON again When water starts overflowing through the drain line set the switch to operation I position The unit is now ready to resume normal operation 17 Place again the evaporator cover and the unit service panels 18 At completion of the freezing and harvest cycle make sure of proper texture and clearness of the ice cubes and that they do not have any aci...

Отзывы: