Adjustments
Bridge Thickness - For the Service Tech Only
1.
Remove left louver, locate controller on and off
switches.
2.
Push and hold Off till the machine stops.
3.
Remove curtain.
4.
Use a hex wrench and rotate the bridge
thickness adjustment screw in 1/8 turn
increments CW to increase bridge thickness.
Rotate CCW to decrease bridge thickness.
Caution: Do not make the bridge too thin or the
machine will not harvest properly. Bridge thickness
adjustments are not covered by warranty.
5.
Return curtain and louver to their normal
positions.
6.
Push and release the On button. Check next
harvest of ice. Repeat steps 1-6 if needed.
Water Purge Setting
The water purge is factory set to the automatic
position, suitable for most water conditions. The
setting can be changed to one of 5 manual settings
or left on automatic.
Purge
setting
1 - Minimum
2 -
Moderate
3 -
Standard
4 - Heavy
5 - Maximum
A - Automatic
Water
Type
RO water or
equivalent
Low TDS
non - RO
water
Use for
typical
water
High TDS
water
Very High
TDS water
Any with
conductivity not
less than 10
microSiemens/cm
To set:
1.
Switch the machine OFF by holding the Off
button in until a number or the letter
A
shows
on the display.
2.
Press and release the On button repeatedly
until the number on the display corresponds to
the desired setting.
3.
Press and release the Off switch again to
return to the normal control state.
2007
Page 9
CU1526, CU2026, CU3030
Installation Manual
Bridge Thickness Adjustment Mechanism
Ice Bridge Thickness Measurement
Adjustment
Screw
Too Big
Too Small
Just Right
3 - 4 mm
bridge
Note: Water cooled models, the refrigeration
system discharge pressure is factory set at 245
PSIG or 1700 kPa (gauge) or 17 Bar, which should
yield a freeze cycle discharge water temperature of
about 50 - 43 degrees C. Adjust if necessary.