CME256, 506, 656, 806: AutoIQ™ Cubers
June 2002
Page 30
Operational Characteristics:
CME806
Cycle Times (minutes)
System Pressures
A - E Series Refrigerant Charge, R-404A
•
Air cooled: 33 ounces
•
Water cooled: 24 ounces
F Series Refrigerant Charge, R-404A
•
Air cooled: 33 ounces
•
Water cooled: 26 ounces
Typical Compressor Amps
•
Freeze: single phase = 13
•
Harvest: single phase = 14
Typical Harvest Ice Weight
•
6.5 - 7 lb.
Water Cooled:
•
Discharge Pressure: 240 - 245 PSIG
•
Hi Pressure Cuts Out at: 450 PSIG
Fan Control Switch - for units so equipped:
•
Cut In: 240 PSIG + - 20 PSIG
•
Cut Out: 190 PSIG + - 10 PSIG
Air Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Freeze
9 - 11
12 - 14
Harvest
1:45
1:15
Water Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Freeze
10 - 12
12 - 13
Harvest
1:45
1:15
Air Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Suction: End of Freeze
20 - 21
25 - 27
Suction: Peak in Harvest
89 - 91
115 - 125
Discharge: 5 minutes into Freeze
210 - 220
280 - 290
Discharge: Minimum in Harvest
155
205
Water Cooled
70
o
F. indoor air, 50
o
F. water
90
o
F. indoor air, 70
o
F. water
Suction: End of Freeze
24 - 26
24 - 26
Suction: Peak in Harvest
85 - 95
90 - 95
Discharge:
240 PSIG
240 PSIG
Discharge: Minimum in Harvest
155
165