6.

 

Operation 

6.1

 

Normal use 
The F-Link network is designed to be transparent in normal use.  The linked systems will communicate with each 

other using the F-Link as a wireless bridge.  The display on each F-Link provides status information and gives 

details of alarm messages.  Any alarms or faults are signalled by relay outputs to the controlling equipment for 

notification as required. 
Daily: 

Each F-Link unit status display should be visually checked and any faults reported to the relevant 

maintenance organisation. 

Weekly:  Send a signal between all F-Link units and check that they are communicating correctly (this might be 

as  part  of  the  normal  weekly  fire  alarm  test).    Any  issues  should  be  reported  to  the  relevant  

maintenance organisation. 

At an appropriate maintenance interval (e.g. 6 months) the F-Link network should be thoroughly tested for full 

and correct operation by a suitable maintenance organisation, normally as part of the maintenance of the linked 

system/s (e.g. Fire Alarm System). 
Any faults detected by the F-Link system are reported on the display, by triggering the fault relay, and operating 

a local fault sounder.  This sounder can be muted by pressing the SND MUTE button, but it will re-start if a new 

condition is detected. 

6.2

 

Status LED’s 

 

POWER:  Unit has power. 

 

ZONE:  A zone input or output is 

active. 

 

FAULT (ON):  Indicates a 

communication fault, 

either local (FP-Link) or 

radio (Link Fail). 

 

FAULT (FLASH):  Test mode is active. 

 

RESET:  Unit is resetting (via key 

or remote input). 

 

TRANSMIT:  Unit is transmitting, 

either to update zone 

status or as a regular (30 

sec) announcement / 

poll. 

 

DISPLAY:  Scrolls to show details of 

all current events.  Any 

‘Priority’ events are 

shown on top of other 

messages. 

6.3

 

Reset 
The default configuration for the F-Link units is for the outputs to self-reset once clear.  However, if any outputs 

have been set to operate in Latched mode then they will need to be manually reset once triggered. 
To reset the F-Link, insert the key into the keyswitch on the underside and turn to the reset position then return 

to normal.  The F-Link will reset and clear any triggered zones. 

6.4

 

Test mode 
Each F-Link can be placed in test mode using the keyswitch on the underside of the unit.  F-Links in test mode 

will beep intermittently and operate their fault relay to warn of the impairment, as will the Master.   Whilst in 

test  mode  the  F-Link  will  not  trigger  its  output  relays  or  cause  other  F-Links  to  trigger  their  output  relays,  

although messages are displayed as usual (so that message transmission can be checked).  Any F-Links not in 

test mode will operate as usual. 

Содержание F-LINK MK4

Страница 1: ...ef FLNK4red Page 1 of 23 Issue 1 F LINK MK4 INSTALLATION MANUAL Scope Communications UK Ltd Quantum House Steamer Quay Rd Totnes Devon TQ9 5AL Tel 44 0 1803 860700 Fax 44 0 1803 863716 Email sales scope uk com Web www scope uk com ...

Страница 2: ...roducts are designed to operate safely when installed and used according to general safety practices The following requirements should be observed at all times This equipment is designed for indoor use unless expressly stated otherwise and must not be used in classified Hazardous Areas including areas containing explosive or flammable vapours unless express authorisation has been given in writing ...

Страница 3: ...hardware 9 3 1 1 Antennas 9 3 1 2 Range considerations 10 3 1 3 Environment 10 3 1 4 Mounting height 10 3 1 5 Interconnect cabling 10 3 2 Connections 10 3 2 1 Power connection 10 Zone inputs 15 3 2 2 FP link input 15 3 2 3 Reset input 15 3 2 4 Zone outputs 15 3 2 5 Link Fail output 15 3 2 6 Wiring diagrams 16 4 Configuration 17 4 1 Overview 17 4 2 General tab 17 4 3 Units tab Global 17 4 3 1 Prior...

Страница 4: ...lude text descriptors for each Node and each zone event zone input type and output relay operating mode The address of each Node is set on site using dip switches as is the frequency channel used by the system An optional F Link paging transmitter can be added to the system to send alarm and fault event descriptions to portable belt worn pagers An optional interface can be fitted to provide a seri...

Страница 5: ...ox 30 suggests the chosen frequency channel is probably suitable for use If any signals are witnessed over this level then an alternative frequency channel should be selected and the check repeated See 2 1 3 overleaf for details on how to change the frequency channel Maximum acceptable background signal level Background signal level too high try a different channel Strong interfering signal try a ...

Страница 6: ...ct the required frequency channel The F Link will detect the change and reboot displaying the selected frequency All F Links on a system must be set to use the same frequency channel If an unavailable channel is selected e g channel 26 the F Link will automatically use the closest available channel The actual frequency in use is displayed each time the F Link reboots ...

Страница 7: ... into network join mode Press and hold the join switch on the Master F Link until it displays LISTENING FOR NODES 2 Join each Node to the network Press and hold the join switch on any one Node until it displays JOINING NETWORK CONTACT MASTER Once joined it will display SUCCESSFULLY JOINED NETWORK and then reset Repeat step 2 for each Node in turn Any un joined Nodes will continue to display NOT JO...

Страница 8: ... every F Link on the system By default outputs 1 3 are set as Follow and output 4 is set as Class Change Follow The output will clear when the input is cleared This is the default mode for outputs 1 3 Momentary The output will clear after a set period max 125 seconds regardless of the input state Latched The output will remain switched until manually reset using the keyswitch or external reset inp...

Страница 9: ...programming at this pre installation stage before the units are installed in their final locations 3 Installation 3 1 Siting the hardware Before positioning the hardware in a specific location it is important to take into account a number of factors as set out below 3 1 1 Antennas Never operate any Scope equipment without a suitable antenna connected The F Link can communicate over a considerable ...

Страница 10: ... a fire alarm system 3 1 4 Mounting height The display screen should be mounted in a location and at a height where it can be easily read by the end user Easy access to the control keyswitch on the underside of the unit will be required for reset purposes and to place the system in test mode for routine maintenance 3 1 5 Interconnect cabling A further consideration is the distance between the tran...

Страница 11: ..._________________________________________________________________ Name of engineer _____________________________________________________________________________ Date of commissioning _________________________________________________________________________ Default Name Configured Name Location if different Joined Rec d Signal Master MAIN BUILDING 100 Node 1 BUILDING 1 Node 2 BUILDING 2 Node 3 BUIL...

Страница 12: ...ntary Latched Class Change Priority Display 1 2 3 4 Input type Node Zone M 1 2 3 4 5 6 7 NO NC NO NC NO NC NO NC NO NC NO NC NO NC NO NC 1 2 3 4 Node Zone 8 9 10 11 12 13 14 15 NO NC NO NC NO NC NO NC NO NC NO NC NO NC NO NC 1 2 3 4 By default all inputs are Normally Open NO ...

Страница 13: ...k Mk4 Supervised Transceiver System Zone messages 0 7 Zn Trigger Message Clear Message MASTER 1 2 3 4 NODE 1 1 2 3 4 NODE 2 1 2 3 4 NODE 3 1 2 3 4 NODE 4 1 2 3 4 NODE 5 1 2 3 4 NODE 6 1 2 3 4 NODE 7 1 2 3 4 ...

Страница 14: ...k4 Supervised Transceiver System Zone messages 8 15 Zn Trigger Message Clear Message NODE 8 1 2 3 4 NODE 9 1 2 3 4 NODE 10 1 2 3 4 NODE 11 1 2 3 4 NODE 12 1 2 3 4 NODE 13 1 2 3 4 NODE 14 1 2 3 4 NODE 15 1 2 3 4 ...

Страница 15: ...al key reset function or wired in parallel to it so the F Link can be reset either remotely or using the key See page 20 for details of the reset function This input is volt free and can be triggered by dry contact only do not apply voltage to this or any other control input 3 2 4 Zone outputs Each F Link has four zone output relays which will switch over when the corresponding input is triggered ...

Страница 16: ...F Link Mk4 Supervised Transceiver System Ref FLNK4red Page 16 of 23 Issue 1 3 2 6 Wiring diagrams ...

Страница 17: ...he required changes to the configuration see details below 8 Go to the File menu click Save As and save the modified configuration to your laptop or PC with a different filename 9 Click the Write button to write the modified configuration back to the Master 10 Acknowledge the success message then click DISCONNECT The Master F Link will now wirelessly distribute the changed configuration around the...

Страница 18: ...g monitored by the Master Nodes which have a Network ID set but are not shown as joined are historic they have been joined at some point but are not currently part of the network or have had their node address changed 5 Network Changes The F Link network is designed to be resilient and self healing A copy of the entire system configuration is stored in every Node and can be restored by the system ...

Страница 19: ...is essential 2 Power down the old Master 3 Set the frequency and address dip switches of the new Master to exactly match the old Master 4 Power up the new Master 5 Put one of the existing Nodes into Network Join Mode and join the new Master to the network see the Network Join Procedure on page 7 Note that only the new Master and one existing Node need to be joined the existing Nodes will remain co...

Страница 20: ...be muted by pressing the SND MUTE button but it will re start if a new condition is detected 6 2 Status LED s POWER Unit has power ZONE A zone input or output is active FAULT ON Indicates a communication fault either local FP Link or radio Link Fail FAULT FLASH Test mode is active RESET Unit is resetting via key or remote input TRANSMIT Unit is transmitting either to update zone status or as a reg...

Страница 21: ...k cannot draw enough current quickly enough when it needs to transmit then this can stop signals getting through Site attenuation signal being blocked by walls etc Conduct a radio survey to establish achievable coverage and the optimum aerial type and location Depending on the survey results relocate upgrade aerials as required see 3 1 1 on page 9 Zone stuck on not resetting Zone input still activ...

Страница 22: ...d 8 17 liability 2 lid removal 4 link fail 15 21 listening for nodes 7 logging 4 maintenance 20 master address 7 name 8 replacing 19 messages 8 17 modification 4 momentary 8 17 18 mounting height 10 network 7 18 network join 7 node adding 18 address 7 deleting 18 name 8 replacing 19 noise on channel 21 normally open closed 8 15 paging 4 PC configuration 17 power supply 10 21 priority 9 17 radio su...

Страница 23: ... to normally open or normally closed 1 x volt free fault input 680 end of line triggered by open or short circuit 1 x volt free remote reset input normally open Outputs 4 x configurable volt free zone output relay 1 x fault test output relay all changeover relays 50V 0 5A max Text descriptions Individual Node name 16 characters 4 x input trigger messages 16 characters each 4 x input clear messages...

Отзывы: