UMT/WG T BT Rev3.0 – 08/10/2021
Using this diagram you can calculate refrigerant
charge related to the evaporator inner volume.
Using this diagram you can calculate refrigerant
charge related to the pipe diameter and length. You
can refer even to the following table.
Pipe length (m)
Liquid
line
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
K65 -
120bar
3/8’’(gr)
230
270
320
360
410
460
500
550
590
640
680
730
770
820
860
910
K65 –
120bar
1/2’
(gr)
410
490
570
650
730
810
900
980 1060 1140 1220 1300 1380 1470 1550 1630
K65 –
80 bar
1/2’
(gr)
450
530
620
710
800
890
980 1070 1160 1250 1340 1420 1510 1600 1690 1780
Examples of refrigerant charge calculation
Example 1
Receiver
Standing charge
2.4 kg
PHE Gas cooler
Standing charge
0.21 kg
Evaporator Volume 2 dm
3
Calculated from first graph
0.9 kg
Pipe length 8m x K65 3/8”
Calculated from second graph
0.4 kg
Pump
down
(from
evaporator)
Receiver / Evap
≤
7.2 kg
3.3 kg
0,0
1,0
2,0
3,0
4,0
5,0
6,0
2
4
6
8
10
12
R
efri
ge
ran
t
ch
arg
e
(kg
)
Evaporator Volume (dm3)