© 2017 Surge Suppression, LLC NN00141
Rev. Date: 5/17/2017
Table of Maximum Suggested Operating Voltages and Model Wire Colors
3-Phase
Hi-Leg
∆
3Dx
Model
High Leg (Phase B)
Low Legs (Phases A&C)
*Neutral
to
Ground
Phase
A
Wire
Color
Phase B
(high
leg)
Wire
Color
Phase
C
Wire
Color
Neutral
Wire
Color
Ground
Wire
Color
Nominal
System
Voltage
Voltage
Code
To
Neutral
To
Low Legs
To
GND
To
Neutral
To
Low Leg
To
GND
120/240
3D1
229 V
264 V
229 V
132 V
264 V
132 V
< 132 V
Black
Red
Black
White
Green
*NOTE:
If Neutral to Ground voltage is greater than
5
VAC, a problem may exist in the electrical system. The SPD may be installed; however, a
qualified electrician or Power Quality Engineer should be consulted to correct the problem.
Contact SSI with specific questions.
INSTALLATION STEPS
STEP 1:
Check Voltages
•
Confirm that the system voltage does not exceed the maximum suggested operating voltage. All voltage measurements should be completed with a RMS voltmeter.
DO NOT INSTALL THE FUSED UNIT IF THE MEASURED VOLTAGE EXCEEDS THE MAXIMUM SUGGESTED OPERATING VOLTAGE OF THE DEVICE.
CAUTION: Do not proceed further until power has been removed from the electrical system.
STEP 2:
Mounting the Unit
Non-lug type SPDs are provided with 18-24 inches of #10 AWG/TEW stranded wire. For best performance, mount the SPD so that all wires (phase, neutral, and ground) can
be cut and connected in the shortest, straightest path possible, the goal being 6 inches of wire length or less. For every inch of conductor longer than 6-inches, you increase
the let-through voltage of the SPD by 21.7 volts for an ANSI/IEEE Category B, 6 kV, 3 kA impulse and reduce the performance of the SPD.
•
No sharp bends should be made in the installation. If bends are unavoidable, make them smooth and flowing. The device contains no position-dependent
components; therefore, the device can be mounted upside down or sideways, etc.
•
Do not cut any wires until SPD has been mounted. Units with plastic hubs must be installed with the non-metallic flexible conduit and extra hub.
•
While holding the SPD on the wall, determine the shortest, straightest distance between the hub on the suppressor and hub to be installed on panel. Cut the flexible
conduit to the shortest length possible to fit securely over both hubs.
•
Twist the trimmed flexible conduit onto the extra hub. Slide conduit and hub over wires of SPD and twist the conduit onto the hub of the SPD.
•
Connect the extra hub to the panel and mount the SPD to the wall.
STEP 3:
Connecting “Optional Form C” Dry Relay Contacts (Applies to only to SPDs with optional Dry Relay Contacts)
•
Make sure power is removed from surge suppressor.
•
Open surge suppressor lid and note encapsulant height prior to drilling or punching enclosure. (Allow internal clearance for locknuts.)
•
Drill 0.5” diameter clearance hole through side, top or bottom of unit and install a watertight strain relief (i.e.: Altech #225-A00 (Part No. SR011).
•
NOTE:
Surge suppressor is equipped with two sets of contacts. The first set (labeled 1 & 2, N/C) is normally closed and the other set (labeled 3 & 4, N/O) is normally
open with power applied.
•
Contacts are rated at 60 W (from 30 VDC @ 2 A to 150 VDC @ 0.4 A) or 100 VA (from 50 VAC @ 2A to 220 VAC @ 0.45 A).
•
Alarm contacts accept AWG #26 (0.14mm
2
) to AWG #16 (1.5mm
2
) wire. Wire size must be in compliance with NEC/CEC, State or Local codes for power on circuit.
Follow rules for the class of wiring used when routing alarm leads. To maintain NEMA-4 (IP66) rating use appropriate cable and watertight strain relief.
•
Connect alarm circuit(s) to Normally Open (N/O) or Normally Closed (N/C) terminals as required.
•
Upon replacing front cover of suppressor, certain models allow various lid rotations (90° to 180°) for improved label orientation. (model specific)
STEP 4:
Wire the SPD into the Electrical System
•
Carefully lay out the wires keeping them as short and straight as possible. (Wires may be slow-twisted together thereby reducing RF-impedance.) After a satisfactory
layout has been made to the appropriate termination points as described below, cut the wires and connect them as instructed.
•
Connect the GREEN ground wire from/to the SPD to the system Ground bus bar or to a lug mounted in the can or frame close to the SPD if the Ground bus bar is not
close following the current the NEC/CEC. Refer to earlier sections for systems utilizing an isolated ground. Connect the WHITE neutral wire from/to the SPD to the
system Neutral bus bar.
•
Connect the phase wires or “hot” wires (see table above for wire colors) from the SPD to the
correct
phase conductor or bus of the electrical system (one phase wire to
each phase per the colors in the above table) through the required circuit interrupts (fuses or breakers) described above. ^Note: The “High-Leg” (red) wire is normally
associated with the “B” Phase Lug position; ~208 VAC to ‘N’ or ‘G’, not 120 VAC! Also note that the units have internal fusing and do not require external circuit
interrupts (external fuses or breakers). They may be directly connected to the phase conductors or buses after the main disconnect.
•
Upon replacing front cover of suppressor, certain models allow various lid rotations (90° or 180°) for improved label orientation (< model specific).
Before energizing, measure the voltage again to ensure it is within the levels in the table above.
Immediate failure of the SPD will occur if installed on voltages higher than shown in the Table at the top of this page.
STEP 5:
Apply Power to the SPD
•
The LED status indicators should be illuminated. If not, remove power from the SPD and contact Surge Suppression Incorporated at: 1-(888)-987-8877.