5.23
Date Code 20170601
Instruction Manual
SEL-387-0, -5, -6 Relay
Metering and Monitoring
Status Monitor
Magnitude Limits on
Through-Fault Event
Data
In the above
TFE
command responses, there are limits, besides the
aforementioned 1200 event limit on stored through-fault events, to data
accumulation. These limits are:
➤
“Number of Through Faults” counts: 65,535 counts
➤
“Total I-squared-t” (per phase): 4,294,967.295 kA
2
seconds
➤
“Duration” for through-fault event: 8191 cycles, converted to
seconds
➤
“IA, IB, IC” for through-fault event 65,535 A, primary
If any of these values exceed their limits, a plus sign (+) is appended to the
above maximum limit number in the display. If “Duration” or “IA, IB, IC”
values are at their maximums or beyond, then the monitor uses the above
maximum values in performing subsequent simple I
2
t calculations and
cumulatively storing calculation results for each monitored phase.
All these through-fault event data are stored in nonvolatile memory.
Status Monitor
The status monitor of the SEL-387 is designed to provide information on the
internal health of the major components of the relay. The relay continuously
runs a variety of self-tests. Some tests have warning and failure states; others
only have failure states.
Status Monitor
Report Function
(STATUS Command)
The
STATUS
command displays a report of the self-test diagnostics. The
relay automatically executes the
STATUS
command whenever the self-test
software enters a warning or failure state.
If a warning or failure state occurs, the next time the
STA
command is issued,
the warning state is reported. If a warning or failure occurs, it will not be
cleared until relay power is cycled and the problem is fixed. Saving relay
settings performs a warm boot of relay logic. This may clear some warnings.
If warnings persist, contact the factory.
Below is the
STATUS
report format. All warnings, represented by a
W
in the
status report, generate an automatic serial port message and pulse the
ALARM
output contact for five seconds. All failures, represented by an
F
in the status
report, generate an automatic serial port message, display the failure on the
front-panel display, and latch the
ALARM
output contact.
=>
STA <Enter>
XFMR 1 Date: 04/25/00 Time: 00:23:54.259
STATION A
FID=SEL-387-6-X117-V0-Z001001-D20000419 CID=2001
SELF TESTS
W=Warn F=Fail
IAW1 IBW1 ICW1 IAW2 IBW2 ICW2
OS 2 -0 2 1 1 1
IAW3 IBW3 ICW3 IAW4 IBW4 ICW4
OS 4 3 0 3 2 -0
+5V_PS +5V_REG -5V_REG +12V_PS -12V_PS +15V_PS -15V_PS
PS 4.95 5.00 -5.07 11.98 -12.17 14.92 -14.91
TEMP RAM ROM A/D CR_RAM EEPROM IO_BRD
41.1 OK OK OK OK OK OK
Relay Enabled
Содержание SEL-387-0
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 200: ...This page intentionally left blank ...
Страница 248: ...This page intentionally left blank ...
Страница 380: ...This page intentionally left blank ...
Страница 422: ...This page intentionally left blank ...
Страница 440: ...This page intentionally left blank ...
Страница 458: ...This page intentionally left blank ...
Страница 516: ...This page intentionally left blank ...
Страница 540: ...This page intentionally left blank ...