9.42
SEL-2032
Communications Processor
Instruction Manual
Date Code 20120126
Protocols
Serial Distributed Network Protocol (Serial DNP3)
Step 11. Perform an
AUTO 1
command on the SEL-2032 and you will
see a response similar to that in
indicating that Fast
SER data is available.
Step 12. Configure the SEL-421 SER function to monitor the circuit
breaker position contact called 52AA1 inside the relay as SER
point 1.
Step 13. Configure automatic messaging for the lower-tier SEL-2032
Port 3 to collect 20TARGET data.
This data will act as present state data during SEL-2032
initialization.
Step 14. On the upper-tier SEL-2032, enter the following math/
movement statement on Port 16 (52AA1 is set as SER point 1
in the SEL-421 Relay):
0:1 = 2:STATE:1.0
Step 15. Collect event data with the DNP3 master.
If a trip-reclose-trip event occurs with the circuit breaker
connected to the SEL-421 on the lower-tier SEL-2032, the
DNP3 master will receive three time-stamped events, one for
each circuit breaker trip and close.
The syntax used for the two-tier system is described generically:
a.b = x:STATE:y.z
where the variables have the uses listed in
When configuring a two-tier system, you will need SER point numbers from
the device connected to the lower-tier SEL-2032. To obtain these, print or
display the SER settings for the device. The point number is the number of the
input point, starting with the first point assigned to the SER. For example, in
an SEL-300 series relay, the first point assigned in the SER1 setting (that
contains several SER assignments) is point 1. For an SEL-421, each SER
point is configured in a separate setting line. To find the point number, count
from the first point starting with one to the point that you are going to
configure.
Table 9.24
Two-Tier Fast SER Math/Movement Statement Parameters
Parameter
Definition
a
User Region destination register
b
User Region destination bit of destination register
x
Port connected to lower-tier SEL-2032
y
Port on lower-tier SEL-2032 where Fast SER device is connected
z
SER point number in device (see following discussion)
Содержание SEL-2032
Страница 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 12: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 46: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 70: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 104: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 124: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 244: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 322: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 328: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 336: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 338: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 342: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 348: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Страница 354: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...