4.94
SEL-787 Relay
Instruction Manual
Date Code 20081022
Protection and Logic Functions
Port Settings (SET P Command)
PORT 2
PORT 3
PORT 4
Table 4.44
Fiber-Optic Serial Port Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
PROTOCOL
SEL, DNP, MOD,
EVMSG, PMU, MBA,
MBB, MB8A, MB8B,
MBTA, MBTB
PROTO := SEL
SPEED
300–38400 bps
SPEED := 9600
DATA BITS
7, 8 bits
BITS := 8
PARITY
O, E, N
PARITY := N
STOP BITS
1, 2 bits
STOP := 1
PORT TIME-OUT
0–30 min
T_OUT := 5
SEND AUTOMESSAGE
Y, N
AUTO := N
FAST OP MESSAGES
Y, N
FASTOP := N
MODBUS SLAVE ID
1–247
SLAVEID := 1
NOTE:
For additional settings when
PROTO := MBxx, see
as well
. For
additional settings when
PROTO := DNP, see
for a
complete list of the DNP3 session
settings.
Table 4.45
Rear-Panel Serial Port Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
PROTOCOL
SEL, DNP, MOD,
EVMSG, PMU, MBA,
MBB, MB8A, MB8B,
MBTA, MBTB
PROTO := SEL
SPEED
300–38400 bps
SPEED := 9600
DATA BITS
7, 8 bits
BITS := 8
PARITY
O, E, N
PARITY := N
STOP BITS
1, 2 bits
STOP := 1
PORT TIMEOUT
0–30 min
T_OUT := 5
SEND AUTOMESSAGE
Y, N
AUTO := N
HDWR HANDSHAKING
Y, N
RTSCTS := N
FAST OP MESSAGES
Y, N
FASTOP := N
MODBUS SLAVE ID
1–247
SLAVEID := 1
NOTE:
For additional settings when
PROTO := MBxx, see
as well
. For
additional settings when
PROTO := DNP, see
for a
complete list of the DNP3 session
settings.
Table 4.46
Rear-Panel Serial Port (EIA-232/EIA-485) Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
PROTOCOL
SEL, MOD, DNET,
DNP, EVMSG, PMU,
MBA, MBB, MB8A,
MB8B, MBTA, MBTB
PROTO := SEL
COMM INTERFACE
232, 485
COMMINF := 232
SPEED
300–38400 bps
SPEED := 9600
DATA BITS
7, 8 bits
BITS := 8
PARITY
O, E, N
PARITY := N
STOP BITS
1, 2 bits
STOP := 1
PORT TIMEOUT
0–30 min
T_OUT := 5
SEND AUTOMESSAGE
Y, N
AUTO := N
HDWR HANDSHAKING
Y, N
RTSCTS := N
FAST OP MESSAGES
Y, N
FASTOP := N
MODBUS SLAVE ID
1–247
SLAVEID := 1
NOTE:
For additional settings when
PROTO := MBxx, see
as well
as
.For
additional settings when
PROTO := DNP, see
for a
complete list of the DNP3 session
settings.
Содержание SEL-787
Страница 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Страница 6: ...This page intentionally left blank ...
Страница 12: ...This page intentionally left blank ...
Страница 18: ...This page intentionally left blank ...
Страница 78: ...This page intentionally left blank ...
Страница 206: ...This page intentionally left blank ...
Страница 280: ...This page intentionally left blank ...
Страница 334: ...This page intentionally left blank ...
Страница 376: ...This page intentionally left blank ...
Страница 388: ...This page intentionally left blank ...
Страница 474: ...This page intentionally left blank ...
Страница 508: ...This page intentionally left blank ...
Страница 522: ...This page intentionally left blank ...