Date Code 20191029
Field Reference Guide
SEL-734W and SEL Wireless Current Sensor
SEL-734W and SEL Wireless Current Sensor
Instruction Manual
S E C T I O N
7
Testing and Troubleshooting
provides instructions for troubleshooting and common problems.
Table 7.1
Troubleshooting and Common Problems
Problem
Solution
CLOSE
or
OPEN
Button
Does Not Respond
➤
Check that the Manual mode is enabled. Press the
MANUAL
pushbutton to enable this mode.
➤
Check that the control power is healthy.
➢
Check that the control power fuse located on the inside of the enclosure has continuity.
➢
Check that 120 Vac is present. Refer to the enclosure wiring and check that 120 Vac voltage is pres-
ent between the control power fuse and neutral.
➢
Check the front panel. Refer to the appropriate design template guide to check the SEL-734W indi-
cators of control power.
➤
Check that an overvoltage does not exist. To protect the switches and the capacitor bank, the controller
will not close a switch if an overvoltage condition exists. Refer to
SEL-734W Template Reference Guide
to check the SEL-734W lockout indicators.