4.146
SEL-700G Relay
Instruction Manual
Date Code 20170814
Protection and Logic Functions
Group Settings (SET Command)
Table 4.43
Undervoltage Settings
Setting Prompt
Setting Range
Setting Name :=
Factory Default
a
a
m = X or Y; n = 1—6.
PHASE UV LEVEL
OFF, 2.0–300.0 V
27Pm1P := OFF
PHASE UV DELAY
00.00–120.00 s
27Pm1D := 0.50
PHASE UV LEVEL
OFF, 2.0–300.0 V
27Pm2P := OFF
PHASE UV DELAY
00.00–120.00 s
27Pm2D := 5.00
PH-PH UV LEVEL
OFF, 2.0–300.0 V
b
b
Setting range shown is for DELTAY_m := DELTA.
27PPm1P := 93.5
PH-PH UV LEVEL
OFF, 2.0–520.0 V
c
c
Setting range shown is for DELTAY_m := WYE.
27PPm1P := 93.5
PH-PH UV DELAY
00.00–120.00 s
27PPm1D := 0.50
PH-PH UV LEVEL
OFF, 2.0–300.0 V
27PPm2P := OFF
PH-PH UV LEVEL
OFF, 2.0–520.0 V
27PPm2P := OFF
PH-PH UV DELAY
00.00–120.00 s
27PPm2D := 0.50
ENABLE P-SEQ UV
N, 1–6
E27V1X := 1
POS SEQ UV LEVEL
OFF, 2.0–170.0 V
27V1XnP := 5.0
POS SEQ UV LEVEL
OFF, 2.0–300.0 V
27V1XnP := 5.0
POS SEQ UV DELAY
00.00–120.00 s
27V1XnD := 0.50
SYNC PH UV LEVEL
OFF, 2.0–300.0 V
27S1P := OFF
SYNC PH UV DELAY
00.00–120.00 s
27S1D := 0.50
SYNC PH UV LEVEL
OFF, 2.0–300.0 V
27S2P := OFF
SYNC PH UV DELAY
00.00–120.00 s
27S2D := 0.50
Содержание SEL-700G Series
Страница 14: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 32: ...This page intentionally left blank ...
Страница 52: ...This page intentionally left blank ...
Страница 106: ...This page intentionally left blank ...
Страница 510: ...This page intentionally left blank ...
Страница 560: ...This page intentionally left blank ...
Страница 578: ...This page intentionally left blank ...
Страница 588: ...This page intentionally left blank ...
Страница 604: ...This page intentionally left blank ...
Страница 634: ...This page intentionally left blank ...
Страница 738: ...This page intentionally left blank ...
Страница 802: ...This page intentionally left blank ...
Страница 816: ...This page intentionally left blank ...