B.5
Date Code 20020903
SEL-587Z Instruction Manual
Firmware Upgrade Instructions
Establish Terminal Connection
Figure B.5
Terminal Emulation Startup Prompt.
Failure to Connect
If you do not see the “=” prompt, press
<Enter>
again. If you still do not see
the “=” prompt, you have either selected the incorrect serial communications
port on your computer or the computer speed setting does not match the data
transmission rate of your relay. Perform the following steps to reattempt a
connection.
Step 1. From the Call menu, choose Disconnect to terminate
communication.
Step 2. Correct your port setting.
a. From the File menu, choose Properties.
You should see a dialog box similar to
b. Select a different port in the “Connect using:” list box.
Figure B.6
Correcting Port Setting.
Step 3. Correct communications parameters.
a. From the
filename
Properties dialog box shown in
, click Configure.
b. You will see a dialog box similar to
Step 4. Change settings in the appropriate list boxes to match the
settings you recorded in
and click
OK
.