3-14
Overcurrent, Voltage, Synchronism Check, Frequency, and Power Elements
Date Code 20001006
SEL-351 Instruction Manual
Negative-Sequence Instantaneous/Definite-Time Overcurrent Elements
IMPORTANT
: See
Appendix F
for information on setting negative-sequence overcurrent
elements.
Four levels of negative-sequence instantaneous/definite-time overcurrent elements are available.
Two additional levels of negative-sequence instantaneous overcurrent elements (Levels 5 and 6) are
also available. The different levels are enabled with the E50Q enable setting, as shown in
Figure 3.12 and Figure 3.13.
Level 2 element 67Q2S in Figure 3.12 is used in directional comparison blocking schemes (see
Directional Comparison Blocking (DCB) Logic
in
Section 5: Trip and Target Logic
). All the
other negative-sequence instantaneous/definite-time overcurrent elements are available for use in
any tripping or control scheme.
To understand the operation of Figure 3.12 and Figure 3.13, follow the explanation given for
Figure 3.1, Figure 3.2, and Figure 3.3 in the preceding
Phase Instantaneous/Definite-Time
Overcurrent Elements
subsection, substituting negative-sequence current
3I
2
[3I
2
= I
A
+ a
2
· I
B
+ a · I
C
(ABC rotation), 3I
2
= I
A
+ a
2
· I
C
+ a · I
B
(ACB rotation), where
a = 1
∠
120° and a
2
= 1
∠
-120°] for phase currents and substituting like settings and Relay Word
bits.
Settings Ranges
Setting range for pickup settings 50Q1P through 50Q6P:
0.25 - 100.00 A secondary
(5 A nominal phase current inputs, IA, IB, IC)
0.05 - 20.00 A secondary
(1 A nominal phase current inputs, IA, IB, IC)
Setting range for definite-time settings 67Q1D through 67Q4D:
0.00 - 16000.00 cycles, in 0.25-cycle steps
Setting range for definite-time setting 67Q2SD (used in DCB logic):
0.00 - 60.00 cycles, in 0.25-cycle steps
Accuracy
Pickup:
±
0.05 A secondary and
±
3% of setting (5 A nominal phase current inputs, IA, IB, IC)
±
0.01 A secondary and
±
3% of setting (1 A nominal phase current inputs, IA, IB, IC)
Timer:
±
0.25 cycles and
±
0.1% of setting
Transient Overreach:
±
5% of setting
Pickup and Reset Time Curves
See Figure 3.5 and Figure 3.6.
Содержание SEL-351
Страница 14: ...Courtesy of NationalSwitchgear com ...
Страница 16: ...Courtesy of NationalSwitchgear com ...
Страница 40: ...Courtesy of NationalSwitchgear com ...
Страница 74: ...Courtesy of NationalSwitchgear com ...
Страница 146: ...Courtesy of NationalSwitchgear com ...
Страница 186: ...Courtesy of NationalSwitchgear com ...
Страница 220: ...Courtesy of NationalSwitchgear com ...
Страница 304: ...Courtesy of NationalSwitchgear com ...
Страница 340: ...Courtesy of NationalSwitchgear com ...
Страница 380: ...Courtesy of NationalSwitchgear com ...
Страница 450: ...Courtesy of NationalSwitchgear com ...
Страница 506: ...Courtesy of NationalSwitchgear com ...
Страница 528: ...Courtesy of NationalSwitchgear com ...
Страница 534: ...Courtesy of NationalSwitchgear com ...
Страница 536: ...Courtesy of NationalSwitchgear com ...
Страница 550: ...Courtesy of NationalSwitchgear com ...
Страница 562: ...Courtesy of NationalSwitchgear com ...
Страница 570: ...Courtesy of NationalSwitchgear com ...
Страница 584: ...Courtesy of NationalSwitchgear com ...
Страница 602: ...Courtesy of NationalSwitchgear com ...
Страница 610: ...Courtesy of NationalSwitchgear com ...