6.12
SEL-311C Relay
Instruction Manual
Date Code 20060320
Close and Reclose Logic
Reclosing Relay
The reclosing relay is in one (and only one) of these states (listed in
at any time. When in reset or lockout, the corresponding Relay Word bit
asserts to logical 1, and the LED illuminates. Automatic reclosing only takes
place when the relay is in the Reclose Cycle State.
Lockout State
The reclosing relay goes to the Lockout State if any
one
of the following
occurs:
➤
The shot counter is equal to or greater than the last shot at the
time of reclose initiation (e.g., all automatic reclosing attempts
are unsuccessful—see
➤
Reclose initiation is unsuccessful because of SEL
OGIC
control
equation setting 79RIS (see
Initiate Supervision Settings (79RI and 79RIS, Respectively) on
page 6.17
).
➤
The circuit breaker opens without reclose initiation (e.g., an
external trip).
➤
The shot counter is equal to or greater than last shot, and the
circuit breaker is open (e.g., the shot counter is driven to last
shot with SEL
OGIC
control equation setting 79DLS while open
interval timing is in progress. See
to-Last Shot Settings (79DTL and 79DLS, Respectively) on
page 6.19
).
➤
The close failure timer (setting CFD) times out (see
).
➤
SEL
OGIC
control equation setting 79DTL = logical 1 (see
Drive-to-Lockout and Drive-to-Last Shot Settings (79DTL and
79DLS, Respectively)
).
➤
The Reclose Supervision Limit Timer (setting 79CLSD) times
out (see
).
➤
A new reclose initiation occurs while the reclosing relay is
timing on an open interval (e.g., flashover in the tank while
breaker is open).
The
OPEN
(
OPE
) command is included in the reclosing relay logic via
SEL
OGIC
control equation settings. For example:
79DTL =
… + OC
(drive-to-lockout)
Relay Word bit OC asserts for execution of the
OPE
command. See
Command (Open Breaker) on page 10.36
for more information on the
OPE
command. Also, see
Drive-to-Lockout and Drive-to-Last Shot Settings
(79DTL and 79DLS, Respectively)
.
Table 6.1
Relay Word Bit and Front-Panel
Correspondence to Reclosing Relay States
Reclosing Relay State
Corresponding
Relay Word Bit
Corresponding
Front-Panel LED
Reset
79RS
RS
Lockout
79LO
LO
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...