6.5
Date Code 20060320
Instruction Manual
SEL-311C Relay
Close and Reclose Logic
Reclose Supervision Logic
Reclose Supervision Logic
Note that one of the inputs into the close logic in
is:
Reclosing Relay Open Interval Time-Out (qualified by 79CLS)
This input into the close logic in
is the indication that a reclosing
relay open interval has timed out, a qualifying condition (SEL
OGIC
control
equation setting 79CLS) has been met, and thus automatic reclosing of the
circuit breaker should proceed by asserting the CLOSE Relay Word bit to
logical 1. This input into the close logic in
reclose supervision logic in the following
.
q
.
Figure 6.2
Reclose Supervision Logic (Following Open Interval Time-Out)
Operation of Reclose Supervision Logic if
timer setting 79CLSD is set:
79CLSD = 0
The above logic satisfies most applications.
Reclose Supervision
Reclosing
Relay Open
Interval Timeout
(qualified by 79CLS)
Reclosing Relay
Open Interval Timeout
(qualified by 79CLS)
q
Reclose Initiate
(If setting 79CLSD = OFF,
the Reclose Supervision Limit Timer
is inoperative and does not time limit
the wait for the Reclose Supervision
condition, 79CLS, to assert to logical 1)
Reclosing
Relay Open
Interval
Timeout
79RI
79CLSD = OFF
Lockout
Reclose
Supervision
Limit Timer
Reclose Supervision
CLOSE
79LO
79CLSD
0
SEL
OGIC
Setting
52A
SEL
OGIC
Settings
79CLS
SEL
OGIC
Setting
RCSF
Relay
Word
Bit
RCSF
Relay
Word
Bit
Relay
Word
Bits
79CLS
Reclosing
Relay Open
Interval
Timeout
Rising Edge
Detect
Rising Edge Detect
Reclose Supervision
Failure:
Pulses (logical 1) for one
processing interval if
Reclose Supervision
Limit Timer times out
(drives reclosing relay
to lockout)
Reclose Supervision Failure
Pulses (logical 1) for one
processing interval if
SEL
OGIC
control equation
setting 79CLS is not
asserted to logical 1 at the
instant a reclosing relay
open interval timer times
out (drives reclosing relay
to lockout)
Operation of Reclose Supervision Logic if
timer setting 79CLSD is set:
79CLSD
≠
0
(e.g., 79CLSD = 60)
The logic below is used only in a few,
unique applications.
q
Содержание SEL-311C
Страница 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Страница 22: ...This page intentionally left blank ...
Страница 42: ...This page intentionally left blank ...
Страница 68: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 294: ...This page intentionally left blank ...
Страница 330: ...This page intentionally left blank ...
Страница 402: ...This page intentionally left blank ...
Страница 406: ...This page intentionally left blank ...
Страница 454: ...This page intentionally left blank ...
Страница 574: ...This page intentionally left blank ...
Страница 592: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 648: ...This page intentionally left blank ...
Страница 652: ...This page intentionally left blank ...
Страница 678: ...This page intentionally left blank ...
Страница 682: ...This page intentionally left blank ...
Страница 722: ...This page intentionally left blank ...
Страница 724: ...This page intentionally left blank ...
Страница 732: ...This page intentionally left blank ...
Страница 748: ...This page intentionally left blank ...