Date Code 20210715
SEL-2890 Instruction Manual
Detailed Application Examples
Job Done Example 2
4.5
SUBNET_MASK=255.255.255.0
GATEWAY=192.168.0.1
MAC=(not a setting, use factory default)
Next, start the
AC
SEL
ERATOR
QuickSet software and configure
it to communicate with your SEL-2890. Open the
Communication
menu and select
Parameters
to display the dialog
box shown in Figure 4.4.
Figure 4.4
Network Parameters Dialog Box
Next, open the Terminal window by selecting
Terminal
on the
Communication
menu. This will connect you to the SEL-2030. If
you press return, you will see the SEL-2030 prompt. Log in to
Access Level 1 using the
ACC
command and entering the
SEL-2030 password. Next, enter the
PORT 9 D
command to
establish a direct transparent connection with the relay. The
SEL-2030 will not collect SCADA data from the relay while
you are connected with a direct transparent connection. You