ECO-X / IL-X Manual
IM100117
RD: NOV 2009
RL: 05A - BA
25
IS THERE VOLTAGE FROM IGNITION
CONTROL TO COMBINATION GAS
VALVE?
→
CHECK ELECTRICAL WIRES FROM IGNITION
CONTROL TO COMBINATION GAS VALVE
→
CHECK IGNITION CONTROL, REPLACE IF
NECESSARY
NO
IS GAS COMING THROUGH
ORIFICE ON THE HEATER?
YES
→
ENSURE ALL GAS VALVES ARE OPEN
NO
YES
DOES THE IGNITION CONTROL
TERMINATE THE SPARKING
PROCESS AFTER THE HEATER IS
OPERATING?
→
CHECK SPARK IGNITER FOR CRACKS,
REPLACE SPARK IGNITER IF NECESSARY
→
ENSURE THE SENSING WIRE IS SECURELY
CONNECTED TO THE SENSING PROBE
→
CLEAN THE SENSING PROBE ON THE SPARK
IGNITER
→
ENSURE THE FLAME SENSOR IS WITHIN 1/4"
ABOVE THE CERAMIC TILE
→
CHECK FLAME SIGNAL WITH METER, IF LOW
CHANGE
SENSOR
→
REPLACE WITH NEW IGNITION CONTROL
UNIT IF OTHER CHECKS ARE OK
DOES HEATER SHUT DOWN
AFTER IGNITION CEASES?
→
CHECK FLAME SIGNAL USING A METER
INSTALLED IN SERIES WITH SENSOR CABLE,
CHECK (MICROAMPS) STRENGTH OF SIGNAL
FOR 1.5uA MINIMUM
YES
YES
NO
NO
STILL HAVING TROUBLE
OPERATING THE HEATER?
→
REPEAT THE ABOVE TROUBLE SHOOTING
PROCEDURES
→
IF THE PROBLEM PERSISTS, CONTACT YOUR
SCHWANK
DISTRIBUTOR.
YES
NO
TROUBLESHOOTING
COMPLETE
→
IF SIGNAL IS LOW REPLACE SENSOR AND
WIRE