SUSPENDED HORIZONTALLY: (long axis level)
TABLE 2: SUGGESTED LAYOUT / MOUNTING DISTANCES FOR COMFORT*
MODEL
TYPICAL
ABOVE
FLOOR
< X >
TYPICAL
BETWEEN
HEATERS
< Y >
TYPICAL
BETWEEN
ROWS
< Z >
ecoSchwank-X 6 - IL-X 25
ecoSchwank-X 10 - IL-X 37
ecoSchwank-X 13 - IL-X 50
ecoSchwank-X 18 - IL-X 75
ecoSchwank-X 26 - IL-X 100
12’ (366 cm)
15' (460 cm)
16' (490 cm)
19' (580 cm)
22' (670 cm)
18' (550 cm)
22' (675 cm)
28' (850 cm)
34' (1040 cm)
40’ (1220 cm)
25' (760 cm)
30' (910 cm)
40' (1220 cm)
60' (1830 cm)
80’ (2440 cm)
FIGURE 3: SUGGESTED LAYOUT FOR COMFORT
* The Mounting distances are suggested, and may vary depending on insulation/heat loss val-
ues, air movement/change, and other site conditions and comfort requirements. If in doubt,
please contact Schwank Design Services.
For ‘spot’ heating, the distance above the floor can be reduced by 2 to 4 feet (61 to 132 cm)
depending upon site conditions.
Y
X
X
Z
X
Z
SUSPENDED AT AN ANGLE 30° ON SHORT AXIS: (long axis level)
Long axis always level
Short axis may
rotate up to 30°
TYPICAL
ABOVE
FLOOR
< X >
TYPICAL
BETWEEN
HEATERS
< Y >
TYPICAL
BETWEEN
ROWS
< Z >
12’ (366 cm)
14' (430 cm)
15' (460 cm)
18' (550 cm)
20' (610 cm)
18' (550 cm)
22' (675 cm)
28' (850 cm)
34' (1040 cm)
40’ (1220 cm)
25' (760 cm)
30' (910 cm)
40' (1220 cm)
60' (1830 cm)
80’ (2440 cm)
MODEL
ecoSchwank-X 6 - IL-X 25
ecoSchwank-X 10 - IL-X 37
ecoSchwank-X 13 - IL-X 50
ecoSchwank-X 18 - IL-X 75
ecoSchwank-X 26 - IL-X 100
Содержание ecoSchwank-X
Страница 20: ...ECO X IL X Manual IM100117 RD NOV 2009 RL 05B BA 20 14 ELECTRICAL WIRING DIAGRAM 24V CONTROL...
Страница 21: ...ECO X IL X Manual IM100117 RD NOV 2009 RL 05A BA 21 15 ELECTRICAL WIRING DIAGRAM LINE VOLTAGE 120V CONTROL...
Страница 32: ...ECO X IL X Manual IM100117 RD NOV 2009 RL 05B BA 32 23 PARTS LIST 1...