Refrigeration System 

 

• 

The refrigeration system is factory charged with 

R-134A

. If the refrigeration 

system has to be serviced and recharged with refrigerant, do not use any other 
than 

R-134A

• 

The 30AC has low refrigerant pressure and high refrigerant pressure switches in 
the control box. The low-pressure switch is an automatic reset switch that will 
protect the compressor in the event of a refrigerant leak. It is set at 15 psi. The 
high-pressure switch is a manually resetting switch. It will shut of when the 
refrigerant pressure is too high due to a dirty condenser, excessive ambient 
temperature, or a blockage in the refrigerant line. It is set a 425 psi. Do not try to 
adjust the settings of these switches. 

• 

This is a medium temperature chiller.  The temperature range is 45 to 90

°

F. The 

chiller will not operate to its full capacity outside of this temperature range. 

• 

This chiller is rated to the ARI (American Refrigeration Institute) standard of 95

°

ambient air temperature and 44

°

F chilled water. The 30AC cannot deliver it’s 

nominal capacity if the ambient temperature exceeds 95

°

F or if the desired 

chilled water is less than 44

°

F. 

 

Chilled Water System 

 

• 

A 100 GPH (Gallons per Hour) positive displacement pump is supplied with this 
chiller.  Because of it’s design, the flow rate is not adjustable. The pressure can 
be adjusted by throttling the discharge. If the discharge is throttled to much, the 
internal pressure relief valve will open and bypass water back through the pump. 
The pressure relief valve is factory set at 60 psi. 

• 

The water used to fill the chiller must be absolutely free of any particulate matter.  
If any particles or sediment is run through the pump it will score the inside, 
resulting in a marked decrease in pump performance. This failure is not covered 
by warranty. A filter is in the discharge line, however the water initially placed in 
the reservoir must be clean. 

• 

The reservoir level must be maintained to the level marked on the sight glass. 
Damage to the evaporator can result due to low water level. 

• 

Plumbing must be rubber hose, PVC, or copper. Use of any other material will 
increase the chance of contamination in the chilled water system. 

• 

The chilled water reservoir is not pressurized. Do not plumb two chillers in series. 

• 

The 30AC has a 5-micron filter with 3/8” FIPT connections. An extra filter 
cartridge is supplied with the chiller. Contact the factory to reorder. 

 
 
 
 
 
 
 

Содержание 30AC

Страница 1: ...S ST TA AL LL LA AT TI IO ON N O OP PE ER RA AT TI IO ON N M MA AI IN NT TE EN NA AN NC CE E O OW WN NE ER RS S M MA AN NU UA AL L Model 30AC Voltage 220 1 Ref Charge R134A Tel 562 926 3855 Fax 562 92...

Страница 2: ...ction Information 6 Installation Instructions 7 Operation 7 Inside Your Chiller 8 Electrical System 8 Refrigeration System 9 Chilled Water System 9 Special Features 10 Service Bulletin 11 Maintenance...

Страница 3: ...Voltage 220 1 Full Load Amps 8 PUMP Pump Specifications 2 5 g p m 60 p s i Nominal Flow Rate 1 6 g p m Nominal Pressure 60 p s i Pump Horsepower 1 3 Pump Type Positive Displacement Pump Material Brass...

Страница 4: ...port on the top of the chiller add water until the level reaches the red line marked on the sight glass DO NOT USE DEIONIZED WATER Connect Discharge and Return Piping Connect your piping to the two fe...

Страница 5: ...l panel This panel will light up and give you a read out of the discharge temperature This unit leave the factor set at 60 F You can read this set temperature by pressing the button on the controller...

Страница 6: ...r level will drop slightly as the pipes are filled Add more water after the unit is started 3 3 OPERATION 1 After all electrical and plumbing connections are made and the reservoir is filled you are r...

Страница 7: ...chiller runs off of 220 1 Volt single phase power It can run at both 60Hz and 50Hz however there is a 12 reduction if cooling capacity and a 17 reduction in flow capacity at 50 Hz The control system a...

Страница 8: ...desired chilled water is less than 44 F Chilled Water System A 100 GPH Gallons per Hour positive displacement pump is supplied with this chiller Because of it s design the flow rate is not adjustable...

Страница 9: ...S FOR MODEL 30AC Chilled Water Filter This unit has a 3 8 clear filter housing with a 3 8 5M cartridge There is an extra cartridge shipped with this unit Water Pump Water pump is rated at 2 5 G P M 60...

Страница 10: ...al or inside the motor compressor enclosure if there is sufficient contaminant air present in the system and an electrical arc occurs as the terminal vents Ignition cannot occur at the venting termina...

Страница 11: ...circuit breaker again opens DO NOT continue to replace or reset as the equipment obviously has an electrical problem CAUTION Continual resetting may cause the terminal to vent 3 DISCONNECT all power...

Страница 12: ...ice Data Book then the internal protector is open and time must be allowed for it to reset Any Common and Start Common and Run and Start and Run resistance reading must be within the values shown in T...

Страница 13: ...motors have permanent lubrication in the bearings The water that is used in the chilled water circuit has no special requirements except that deionized water cannot be used The water should be clean...

Страница 14: ...uns No refrigeration Refrigerant leak Stuck expansion valve Repair leak and recharge Replace expansion valve High pressure trips Condenser motor Air over condenser restricted Service panel not in plac...

Страница 15: ...Pressure Switch Manual Reset Cut out at 425 P S I Low Pressure Switch Automatic Reset Cut out at 15 P S I WORKING REFRIGERANT PRESSURES R 134A High Pressure 185 to 325 P S I Low Pressure 45 to 70 P S...

Страница 16: ...Drier 9 9 1 R160 Evaporator All Copper 9 9 1 R178 Suction Line Heat Exchanger 9 9 1 R182 High Pressure Switch 9 9 1 R183 Low Pressure Switch 9 9 1 Electrical 9 9 E103 Contactors 30 Amps 9 9 2 E104 4 P...

Страница 17: ......

Страница 18: ...eiber or its authorized service agent will replace or at Schreiber s options re pair the part free of charge for materials and labor This warranty does not cover damage caused by misuse accident abuse...

Отзывы: