Schreiber Engineering – Air Cooled Water Chiller 

Model 30 AC – 230/1

 

 
This unit comes completely wired for 230/1. 
 
To test unit as follows.  NOTE:  Make sure that the switch on the panel is off. 
 
Connect close loop water system as marked.  The discharge from chiller water pump to 
heat exchanger being cooled.  Then the return water and the chiller return as marked.  
These discharge and return fittings as 3/8” NPT.  The connecting hose can be rubber or 
plastic.  The discharge pressure can be 60 p.s.i.  Be sure you use a non-contaminate 
hose. 
 
Fill the reservoir through the fill pipe on top of the unit.  Be sure you replace the cap 
when the reservoir’s filled.  The water sight glass is marked at the reservoir proper fill 
level and is also marked for it’s low level. 
 
The unit does have a plug on the electrical cable.  You must install  a  220 plug to match 
your 230/1 power. 
 
With the unit properly plugged into the 230/1 voltage, you can now start the unit by 
turning on the main panel switch.  This switch will start the water pump and give power 
to the solid-state control panel.  This panel will light up and give you a read out of the 
discharge temperature.  This unit leave the factor set at 60

°

F.  You can read this set 

temperature by pressing the button on the controller marked press to adjust should you 
want to change the cut out temperature there is a small screw driver slot to make this 
adjustment. Never set below 45 

°

F to prevent freezing of the reservoir coil.  

 
 
With he controller set at the proper temperature it will control this temperature within 

±

1

°

 

F. 
 
In our wiring system is a low-pressure control.  This control is set at 15 p.s.i.  It is there 
to protect the refrigeration system if there is a refrigerant leak.  This control has an 
automatic reset.  Then the wire in series with this control is a high-pressure control.  
Should the pressure in the refrigeration system reach over 422 p.s.i. this control will cut 
out the voltage.  This control is manual reset.  Do not try to adjust these controls. 
 
A NOTE OF CAUTION:  Always keep the fluid in the reservoir at it’s proper level.  If the 
unit condenser becomes clogged it must be cleaned. Be sure you check the condenser 
often. Does not take much dirt in condenser to cause a problem.  
 
The refrigeration system is a medium temperature.  Never set the controller below 45

°

F. 

 
 
 

Содержание 30AC

Страница 1: ...S ST TA AL LL LA AT TI IO ON N O OP PE ER RA AT TI IO ON N M MA AI IN NT TE EN NA AN NC CE E O OW WN NE ER RS S M MA AN NU UA AL L Model 30AC Voltage 220 1 Ref Charge R134A Tel 562 926 3855 Fax 562 92...

Страница 2: ...ction Information 6 Installation Instructions 7 Operation 7 Inside Your Chiller 8 Electrical System 8 Refrigeration System 9 Chilled Water System 9 Special Features 10 Service Bulletin 11 Maintenance...

Страница 3: ...Voltage 220 1 Full Load Amps 8 PUMP Pump Specifications 2 5 g p m 60 p s i Nominal Flow Rate 1 6 g p m Nominal Pressure 60 p s i Pump Horsepower 1 3 Pump Type Positive Displacement Pump Material Brass...

Страница 4: ...port on the top of the chiller add water until the level reaches the red line marked on the sight glass DO NOT USE DEIONIZED WATER Connect Discharge and Return Piping Connect your piping to the two fe...

Страница 5: ...l panel This panel will light up and give you a read out of the discharge temperature This unit leave the factor set at 60 F You can read this set temperature by pressing the button on the controller...

Страница 6: ...r level will drop slightly as the pipes are filled Add more water after the unit is started 3 3 OPERATION 1 After all electrical and plumbing connections are made and the reservoir is filled you are r...

Страница 7: ...chiller runs off of 220 1 Volt single phase power It can run at both 60Hz and 50Hz however there is a 12 reduction if cooling capacity and a 17 reduction in flow capacity at 50 Hz The control system a...

Страница 8: ...desired chilled water is less than 44 F Chilled Water System A 100 GPH Gallons per Hour positive displacement pump is supplied with this chiller Because of it s design the flow rate is not adjustable...

Страница 9: ...S FOR MODEL 30AC Chilled Water Filter This unit has a 3 8 clear filter housing with a 3 8 5M cartridge There is an extra cartridge shipped with this unit Water Pump Water pump is rated at 2 5 G P M 60...

Страница 10: ...al or inside the motor compressor enclosure if there is sufficient contaminant air present in the system and an electrical arc occurs as the terminal vents Ignition cannot occur at the venting termina...

Страница 11: ...circuit breaker again opens DO NOT continue to replace or reset as the equipment obviously has an electrical problem CAUTION Continual resetting may cause the terminal to vent 3 DISCONNECT all power...

Страница 12: ...ice Data Book then the internal protector is open and time must be allowed for it to reset Any Common and Start Common and Run and Start and Run resistance reading must be within the values shown in T...

Страница 13: ...motors have permanent lubrication in the bearings The water that is used in the chilled water circuit has no special requirements except that deionized water cannot be used The water should be clean...

Страница 14: ...uns No refrigeration Refrigerant leak Stuck expansion valve Repair leak and recharge Replace expansion valve High pressure trips Condenser motor Air over condenser restricted Service panel not in plac...

Страница 15: ...Pressure Switch Manual Reset Cut out at 425 P S I Low Pressure Switch Automatic Reset Cut out at 15 P S I WORKING REFRIGERANT PRESSURES R 134A High Pressure 185 to 325 P S I Low Pressure 45 to 70 P S...

Страница 16: ...Drier 9 9 1 R160 Evaporator All Copper 9 9 1 R178 Suction Line Heat Exchanger 9 9 1 R182 High Pressure Switch 9 9 1 R183 Low Pressure Switch 9 9 1 Electrical 9 9 E103 Contactors 30 Amps 9 9 2 E104 4 P...

Страница 17: ......

Страница 18: ...eiber or its authorized service agent will replace or at Schreiber s options re pair the part free of charge for materials and labor This warranty does not cover damage caused by misuse accident abuse...

Отзывы: