Instructions for Use
– SCHMIDT
®
Flow Sensor SS 20.700
Page 15
Adjust sensor manually at sensor enclosure by turning it counterclock-
wise by approx. 80° to flow direction (observe flow arrow on enclosure
cover). Make sure that immersion depth is maintained.
Tighten spigot nut slightly by means of a key wrench (AF24) to fasten
the sensor.
Apply a key wrench (AF27) to hexagon bolt of the compression fitting
to lock it. Use another key wrench (AF24) to tighten spigot nut of the
compression fitting until the arrow on the sensor enclosure complies
with the direction of the pipe flow.
Check the set angular position carefully, for example by placing a bub-
ble level on the alignment plane of the sensor enclosure.
The angular deviation should not be more than
3°, related to
the ideal measuring direction. Otherwise, measurement accu-
racy may be affected.
In case of wrong adjustment, the compression fitting has to be loos-
ened and the alignment procedure must be repeated.
Shorten safety chain by removing superfluous chain links so that the
chain is slightly tensioned after being locked at the enclosure. Finally,
secure chain with a its padlock.
General note:
Do not use the alignment plane of the enclosure for mechanical
adjustment, e.g. for locking.
There is risk of damage to the sensor.
Mounting of remote version
The sensor probe of the remote version is mounted with a compression
fitting in the same way as the compact sensor.
A wall mounting bracket is provided for fastening the sensor enclosure.