Operating instructions
Hinge safety switch

TESZ

EN

4.  Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by 
 authorised personnel in a de-energised condition. For the 
cable entry, only use suitable plastic cable glands and for 
the connector suitable plugs with an appropriate degree of 
protection must be used.

1. Remove the switching block prior to the wiring (Fig. 1).
2.  If necessary, break out one or both removable openings using a 

suitable tool. Fit the plastic cable glands M20 x 1.5 with gaskets.

3.  Pull the cable through the gland. Connect the wires and cables.  

The contact labelling can be found on the contact elements.

4.  Put back the switching block in the enclosure (Fig. 2). The cable  

must be laid so that no mechanical stress is exerted on the switch in-
serts. Tighten the wires and cables, check cable fixation and arrange 
the inner cables and wires.

5.  After wiring, the wiring compartment must be cleaned (i.e. remove 

excess cables etc.).

6.  The fixing screws for the wiring compartment cover must be tight-

ened uniformly with 0.8 Nm tightening torque.

After the switch has been fitted, the switching function and the opening 
angle of the safety guard must be checked. The aperture angle of the 
NC contacts set in factory is approx. 3.5 ...4° (for version ...5° approx. 

4 … 6°; for version ...8° approx. 6 … 8.5°).  Please observe that during 

the wiring the individual switch inserts nor the complete contact blocks 
are mixed up, otherwise the preset switching angle is no longer guar-
anteed.

Fig. 1

2

1

2

3

3

4

1

1

2

Z10.1

MM/JJJJ

250V

AC/2A

A

24VDC/1A

J

C

U

S

C300

Safety Component

1

2

Fig. 2

4.2  Contact variants

Contacts are shown with safety guard closed.

TESZ..10..

TESZ..102..

TESZ..110..

31

32

A

11
23

12
24

A

11
21

12
22

A
A

TESZ..1102..

TESZ..1110..

11
31
23

12
32
24

A
A

11
21
31

12
22
32

A
A
A

TESZ..1102ST..

3

2

1

4 5 6 7 8

A

11

31

23

12

32

24

A

5

8

4

3

2

1

7

6

Accessories

Connecting cable with  
M12 coupling, 8 pole

Cable length  
5 m

5

8

4

3

2

1

7

6

1 WH

straight

101183472

2 BN
3 GN
4 YE
5 GY
6 PK
7 BU
8 RD

Содержание TESZ

Страница 1: ... below or for the applications authorised by the manufac turer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instruc tions manual the country specific installation standards as well as all prevailing safety regulations and accident prevention ru...

Страница 2: ... must evaluate and design the safety chain in accordance with the relevant standards and depending on the required safety level The entire concept of the control system in which the safety component is integrated must be validated to the relevant standards 2 4 Technical data Standards IEC 60947 5 1 BG GS ET 15 Enclosure glass fibre reinforced thermoplastic self extinguishing Hinge TESZ aluminium T...

Страница 3: ... are preferably fitted in the upper part of the safety guard to avoid the ingress of dirt and soiling as well as damage to the components In case of painting activities the components must be covered The supplied fixing material must be used We recommend that the fixing screws are painted after the component is fitted Please observe the relevant requirements of the standards EN ISO 12100 EN 953 an...

Страница 4: ...res 5 After wiring the wiring compartment must be cleaned i e remove excess cables etc 6 The fixing screws for the wiring compartment cover must be tight ened uniformly with 0 8 Nm tightening torque After the switch has been fitted the switching function and the opening angle of the safety guard must be checked The aperture angle of the NC contacts set in factory is approx 3 5 4 for version 5 appr...

Страница 5: ...Positive break travel angle 5 Set up and maintenance 5 1 Functional testing The safety function of the safety components must be tested The following conditions must be previously checked and met 1 Correct fixing of the component 2 Check the integrity of the cable entry and connections 3 Check the switch enclosure for damage 5 2 Maintenance A regular visual inspection and functional test including...

Страница 6: ...ation of the technical documentation Oliver Wacker Möddinghofe 30 42279 Wuppertal Place and date of issue Wuppertal February 1 2016 Authorised signature Philip Schmersal Managing Director EU Declaration of conformity Original K A Schmersal GmbH Co KG Möddinghofe 30 42279 Wuppertal Germany Internet www schmersal com We hereby certify that the hereafter described components both in their basic desig...

Отзывы: