SRB303SQP-SS

Operating instructions

Safety-monitoring module

EN

6.4  Actuator configuration

Single-channel control with feedback circuit

•  Suitable for increase in capacity or number of contacts by means of 

contactors or relays with positive-guided contacts.

•  If the feedback circuit  

is not required, establish a bridge.

• 

S

 = Feedback circuit

K

A

S

K

A

N

L1

13

14

S2

S1

Dual-channel control with feedback circuit

•  Suitable for increase in capacity or number of contacts by means of 

contactors or relays with positive-guided contacts.

•  If the feedback circuit is not required, establish a bridge.

• 

S

 = Feedback circuit

K

A

K

B

S

13

14

S2

S1

K

A

K

B

N

L1

7.  Set-up and maintenance

7.1  Commissioning

The safety relay module features protection class IP54 for installation in 

a switch cabinet.

7.2  Functional testing

The safety function of the safety-monitoring module must be tested. 

The following conditions must be previously checked and met:

1.  Correct fixing

2.  Check the integrity of the cable entry and connections

3.  Check the safety-monitoring module's enclosure for damage.

4.  Check the electrical function of the connected sensors and their 

influence on the safety-monitoring module and the downstream 

actuators

7.3  Maintenance

A regular visual inspection and functional test, including the following 

steps, is recommended:

1.  Check the correct fixing of the safety-monitoring module

2.  Check the cable for damages

3.  Check electrical function

If a manual functional check is necessary to detect a 

possible accumulation of faults, then this must take place 

during the intervals noted as follows:

•  at least every month for PL e with category 3 or 

category 4 (according to ISO 13849-1) or SIL 3 with HFT 

(hardware fault tolerance) = 1 (according to IEC 62061);

•  at least every 12 months for PL d with category 3 

(according to ISO 13849-1) or SIL 2 with HFT (hardware 

fault tolerance) = 1 (according to IEC 62061).

Damaged or defective components must be replaced.

8.  Disassembly and disposal

8.1  Disassembly

The safety-monitoring module must be disassembled in a de-energised 

condition only.

Push up the bottom of the enclosure and hang out slightly tilted 

forwards.

8.2  Disposal

The safety-monitoring module must be disposed of in an appropriate 

manner in accordance with the national prescriptions and legislations.

Содержание SRB303SQP-SS

Страница 1: ...n accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as well as all prevailing safety reg...

Страница 2: ...ine the Performance Level PL to ISO 13849 1 of the entire safety function e g sensor logic actuator an assessment of all relevant components is required The entire concept of the control system in which the safety component is integrated must be validated to the relevant standards 2 4 Technical data General data Standards EN 60204 1 IEC 60947 5 1 ISO 13849 1 IEC 62061 IEC 61508 EMC rating to EMC D...

Страница 3: ...IN rails to IEC 60715 Snap the bottom of the enclosure slightly tilted forwards in the DIN rail and push up until it latches in position 3 2 Dimensions All measurements in mm Device dimensions H W D SRB303SQP SS PC 100 x 22 5 x 121 mm SRB303SQP SS 120 x 22 5 x 121 mm SRB303SQP SS CC 130 x 22 5 x 121 mm 4 Electrical connection 4 1 General information for electrical connection The electrical connect...

Страница 4: ...KA KB KB KB N L1 6 5 S J Key a Safety inputs b Power c Processing 6 2 Wiring example Function SS Automatic start Dual channel control shown for a safety edge The safety relay module is activated automatically when the feedback circuit is closed Relay outputs Suitable for 2 channel control for increase in capacity or number of contacts by means of contactors or relays with positive guided contacts ...

Страница 5: ... enclosure for damage 4 Check the electrical function of the connected sensors and their influence on the safety monitoring module and the downstream actuators 7 3 Maintenance A regular visual inspection and functional test including the following steps is recommended 1 Check the correct fixing of the safety monitoring module 2 Check the cable for damages 3 Check electrical function If a manual fu...

Страница 6: ...in ID n 0035 Person authorised for the compilation of the technical documentation Oliver Wacker Möddinghofe 30 42279 Wuppertal Place and date of issue Wuppertal July 17 2018 Authorised signature Philip Schmersal Managing Director EU Declaration of conformity Original K A Schmersal GmbH Co KG Möddinghofe 30 42279 Wuppertal Germany Internet www schmersal com We hereby certify that the hereafter desc...

Отзывы: