schmersal SRB303SQP-SS Скачать руководство пользователя страница 3

3

SRB303SQP-SS

Operating instructions

Safety-monitoring module

EN

Ambient conditions: 

Ambient temperature:

 

–25°C … +60°C  

(non condensing)

Storage and transport temperature:

 

–40°C … +85°C  

(non condensing)

Protection class:

 

Enclosure: IP40,  

Terminals: IP20,  

Clearance: IP54

Resistance to shock:

 

10 g / 11 ms

Resistance to vibrations  

 

to IEC 60068-2-6:

 

10 ... 55 Hz, amplitude 0.35 mm

Altitude:

 

max. 2,000 m

The data specified in this manual are applicable when the component is 

operated with rated operating voltage U

e

 ±0%.

2.5   Safety classification 

Standards:

 

ISO 13849-1, IEC 61508, IEC 62061

PL:

 

up to e

Control category:

 

up to 3

DC:

 high

CCF:

 

> 65 points

PFH

D

:

 

≤ 2.0 x 10

-8

 / h

PFD

avg

:

 

1.8 x 10

-4

SIL:

 

up to 3

Service life:

 

20 years

The PFH value of 2.0 × 10

-8

/h applies to the combinations of contact 

load (current through enabling contacts) and number of switching 

cycles (n

op/y

) mentioned in the table below. At 365 operating days per 

year and a 24-hours operation, this results in the below-mentioned 

switching cycle times (t

cycle

) for the relay contacts.

Diverging applications upon request.

Contact load

n

op/y

t

cycle

20 %

525,600

1.0 min

40 %

210,240

2.5 min

60 %

75,087

7.0 min

80 %

30,918

17.0 min

100 %

12,223

43.0 min

3.  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to IEC 60715.

Snap the bottom of the enclosure slightly tilted forwards in the DIN rail 

and push up until it latches in position.

3.2  Dimensions

All measurements in mm.

Device dimensions (H/W/D): 

SRB303SQP-SS/PC:   100 x 22.5 x 121 mm

SRB303SQP-SS:  

120 x 22.5 x 121 mm

SRB303SQP-SS/CC:   130 x 22.5 x 121 mm

4.  Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by  

authorised personnel in a de-energised condition.

To avoid EMC disturbances, the physical ambient  

and operational conditions at the place where the  

product is installed, must meet the provisions laid down  

in the paragraph "Electromagnetic Compatibility (EMC)"  

of EN 60204-1.

5.  Operating principle and settings

5.1  Description of the terminals and LED indications

Pin

Function

LED

Function

A1

Operating voltage  
+24 VDC / 24 VAC /  
115VAC / 230VAC

U

B

U

i

Operating voltage OK  
 
Internal fuse OK

A2

Operating voltage  
0 VDC / 24 VAC /  
115VAC / 230VAC

S1 

Output feedback circuit

S2 

Input feedback circuit / 
Output start circuit

X3 

Input external reset

X4 

Input  
automatic start

Output  
safety edge channel 1

Input  
safety edge channel 1

K1 

Status K1

Output  
safety edge channel 2

Input  
safety edge channel 2

K2 

Status K2

41 / 42

Signalling contact (NC)

51 / 52 

Signalling contact (NC)

51 / 54 

Signalling contact (NO)

13 / 14 
23 / 24
33 / 34

Safety releases

UB

Ui

K1

K2

SRB303

SQP-SS

A2

PE

33 34 41 42

13 14 23 24

A1

3 4 5 6

X3 51 52 54

S2 S1 S2 X4

Содержание SRB303SQP-SS

Страница 1: ...n accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as well as all prevailing safety reg...

Страница 2: ...ine the Performance Level PL to ISO 13849 1 of the entire safety function e g sensor logic actuator an assessment of all relevant components is required The entire concept of the control system in which the safety component is integrated must be validated to the relevant standards 2 4 Technical data General data Standards EN 60204 1 IEC 60947 5 1 ISO 13849 1 IEC 62061 IEC 61508 EMC rating to EMC D...

Страница 3: ...IN rails to IEC 60715 Snap the bottom of the enclosure slightly tilted forwards in the DIN rail and push up until it latches in position 3 2 Dimensions All measurements in mm Device dimensions H W D SRB303SQP SS PC 100 x 22 5 x 121 mm SRB303SQP SS 120 x 22 5 x 121 mm SRB303SQP SS CC 130 x 22 5 x 121 mm 4 Electrical connection 4 1 General information for electrical connection The electrical connect...

Страница 4: ...KA KB KB KB N L1 6 5 S J Key a Safety inputs b Power c Processing 6 2 Wiring example Function SS Automatic start Dual channel control shown for a safety edge The safety relay module is activated automatically when the feedback circuit is closed Relay outputs Suitable for 2 channel control for increase in capacity or number of contacts by means of contactors or relays with positive guided contacts ...

Страница 5: ... enclosure for damage 4 Check the electrical function of the connected sensors and their influence on the safety monitoring module and the downstream actuators 7 3 Maintenance A regular visual inspection and functional test including the following steps is recommended 1 Check the correct fixing of the safety monitoring module 2 Check the cable for damages 3 Check electrical function If a manual fu...

Страница 6: ...in ID n 0035 Person authorised for the compilation of the technical documentation Oliver Wacker Möddinghofe 30 42279 Wuppertal Place and date of issue Wuppertal July 17 2018 Authorised signature Philip Schmersal Managing Director EU Declaration of conformity Original K A Schmersal GmbH Co KG Möddinghofe 30 42279 Wuppertal Germany Internet www schmersal com We hereby certify that the hereafter desc...

Отзывы: