Operating instructions
Safety-monitoring module

SRB301STV.2 /CCV.2 /PCV.2
SRB301STV.3 /CCV.3 /PCV.3

EN

5.4  Functional testing

1.  Switch the supply voltage on
2.  Open safety switches.
3.  Enabling paths must be open.
4.  Close safety switches.
5.  Actuate the automatic start or reset button.
6.  Enabling paths must be closed

5.5  Check of the error detection

Detection "NC contact S11-S12 does not open"

1.  Switch the supply voltage on
2.  Close safety switches.
3.  Actuate the automatic start or reset button.
4.  Enabling paths must be closed
5.  Disconnect terminal S22 (simulates opening)
6.  Enabling paths must be open
7.  Reconnect terminal S22 
8.  Actuate the automatic start or reset button.
9.  Enabling paths must remain open.
10.  Switch the device's voltage off and back on. The initial condition is 

restored.

Detection "NC contact S21-S22 does not open"

1.  Switch the supply voltage on
2.  Close safety switches.
3.  Actuate the automatic start or reset button.
4.  Enabling paths must be closed
5.  Disconnect terminal S12 (simulates opening)
6.  Enabling paths must be open
7.  Reconnect terminal S12 
8.  Actuate the automatic start or reset button.
9.  Enabling paths must remain open.
10  Switch the device's voltage off and back on. The initial condition is 

restored.

5.6  Notes

Signalling outputs must not be used in safety circuits.

Opening the front cover (see Fig. 2)

•  To open the front cover, insert a slotted screwdriver in the top and 

bottom cover notch and gently lift it.

•  When the front cover is open, the electrostatic discharge requirements 

must be respected and observed.

•  After setting, the front cover must be fitted back in position.

Only touch the components after electrical discharge!

Setting the switch (see Fig. 3)

•  The cross-wire short monitoring function (factory setting) is pro

-

grammed by means of the switch underneath the front cover of the 
safety-monitoring module.

•  The switch must only be operated in de-energised condition by means 

of a finger or an insulated blunt tool.

•  Pos. nQS (top): Not cross-wire short proof: QS-LED off 

 

Suitable for 1-channel applications and applications with outputs 
connected to potential in the control circuits.

•  Pos. QS (bottom), Cross-wire short proof: QS-LED on 

 

Suitable for 2-channel applications without outputs connected to 
potential in the control circuits

U

B

U

i

K1

K2
QS

SRB 
301ST

33 23 13 41

X2 S12 S11 A1

34 24 14 42

X3 S22 S21 A2

U

B

U

i

K1

K2
QS

SRB 
301ST

33 23 13 41

X2 S12 S11 A1

34 24 14 42

X3 S22 S21 A2

U

B

U

i

K1

K2
QS

SRB 
301ST

33 23 13 41

X2 S12 S11 A1

34 24 14 42

X3 S22 S21 A2

X2 S12 S11 A1

X3 S22 S21 A2

nQS

QS

Fig. 1

Fig. 2

Fig. 3

6.  Set-up and maintenance

6.1  Functional testing

The safety function of the safety-monitoring module must be tested. 
The following conditions must be previously checked and met:
1. Correct fixing
2. Check the integrity of the cable entry and connections
3.  Check the safety-monitoring module's enclosure for damage
4.  Check the electrical function of the connected sensors and their influ-

ence on the safety-monitoring module and the downstream actuators

6.2  Maintenance

A regular visual inspection and functional test, including the following 
steps, is recommended:
1. Check the correct fixing of the safety-monitoring module
2. Check the cable for damages
3. Check electrical function

The device has to be integrated into the periodic check-ups 
according to the Ordinance on Industrial Safety and Health, 

however at least 1 × year.

Damaged or defective components must be replaced.

Содержание SRB301ST/PCV.2

Страница 1: ...ust be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the...

Страница 2: ...11 S12 and or S21 S22 are opened The safety relevant current paths with the outputs contacts 13 14 23 24 and 33 34 meet the following requirements under observation of a PFH value assessment also refe...

Страница 3: ...for electrical connection As far as the electrical safety is concerned the protection against unintentional contact of the connected and therefore electrically interconnected apparatus and the insulat...

Страница 4: ...ch the components after electrical discharge Setting the switch see Fig 3 The cross wire short monitoring function factory setting is pro grammed by means of the switch underneath the front cover of t...

Страница 5: ...reset button e g welded contacts or manipulations which could lead to an inadvertent restart are detected in this configuration and will result in an inhibition of the operation Automatic start see Fi...

Страница 6: ...he control circuits are detected Cross wire shorts between the control circuits are not detected Category 3 PL e to DIN EN ISO 13849 1 possible Dual channel control of magnetic safety switches accordi...

Страница 7: ...nt EC Directives 2006 42 EC EC Machinery Directive 2004 108 EC EMC Directive 1995 16 EG EC Lift Directive Person authorised for the compilation of the technical documentation Oliver Wacker M ddinghofe...

Страница 8: ...A Schmersal GmbH Co KG M ddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal c...

Отзывы: