Operating instructions
Safety-monitoring module
SRB301STV.2 /CCV.2 /PCV.2
SRB301STV.3 /CCV.3 /PCV.3
EN
5.4 Functional testing
1. Switch the supply voltage on
2. Open safety switches.
3. Enabling paths must be open.
4. Close safety switches.
5. Actuate the automatic start or reset button.
6. Enabling paths must be closed
5.5 Check of the error detection
Detection "NC contact S11-S12 does not open"
1. Switch the supply voltage on
2. Close safety switches.
3. Actuate the automatic start or reset button.
4. Enabling paths must be closed
5. Disconnect terminal S22 (simulates opening)
6. Enabling paths must be open
7. Reconnect terminal S22
8. Actuate the automatic start or reset button.
9. Enabling paths must remain open.
10. Switch the device's voltage off and back on. The initial condition is
restored.
Detection "NC contact S21-S22 does not open"
1. Switch the supply voltage on
2. Close safety switches.
3. Actuate the automatic start or reset button.
4. Enabling paths must be closed
5. Disconnect terminal S12 (simulates opening)
6. Enabling paths must be open
7. Reconnect terminal S12
8. Actuate the automatic start or reset button.
9. Enabling paths must remain open.
10 Switch the device's voltage off and back on. The initial condition is
restored.
5.6 Notes
Signalling outputs must not be used in safety circuits.
Opening the front cover (see Fig. 2)
• To open the front cover, insert a slotted screwdriver in the top and
bottom cover notch and gently lift it.
• When the front cover is open, the electrostatic discharge requirements
must be respected and observed.
• After setting, the front cover must be fitted back in position.
Only touch the components after electrical discharge!
Setting the switch (see Fig. 3)
• The cross-wire short monitoring function (factory setting) is pro
-
grammed by means of the switch underneath the front cover of the
safety-monitoring module.
• The switch must only be operated in de-energised condition by means
of a finger or an insulated blunt tool.
• Pos. nQS (top): Not cross-wire short proof: QS-LED off
Suitable for 1-channel applications and applications with outputs
connected to potential in the control circuits.
• Pos. QS (bottom), Cross-wire short proof: QS-LED on
Suitable for 2-channel applications without outputs connected to
potential in the control circuits
U
B
U
i
K1
K2
QS
SRB
301ST
33 23 13 41
X2 S12 S11 A1
34 24 14 42
X3 S22 S21 A2
U
B
U
i
K1
K2
QS
SRB
301ST
33 23 13 41
X2 S12 S11 A1
34 24 14 42
X3 S22 S21 A2
U
B
U
i
K1
K2
QS
SRB
301ST
33 23 13 41
X2 S12 S11 A1
34 24 14 42
X3 S22 S21 A2
X2 S12 S11 A1
X3 S22 S21 A2
nQS
QS
Fig. 1
Fig. 2
Fig. 3
6. Set-up and maintenance
6.1 Functional testing
The safety function of the safety-monitoring module must be tested.
The following conditions must be previously checked and met:
1. Correct fixing
2. Check the integrity of the cable entry and connections
3. Check the safety-monitoring module's enclosure for damage
4. Check the electrical function of the connected sensors and their influ-
ence on the safety-monitoring module and the downstream actuators
6.2 Maintenance
A regular visual inspection and functional test, including the following
steps, is recommended:
1. Check the correct fixing of the safety-monitoring module
2. Check the cable for damages
3. Check electrical function
The device has to be integrated into the periodic check-ups
according to the Ordinance on Industrial Safety and Health,
however at least 1 × year.
Damaged or defective components must be replaced.