Operating instructions

Safety-monitoring module

SRB-E-402ST

EN

7.  Wiring examples

7.1  Possible applications

All applications for 1 or 2-channel safe evaluation for protective 

equipment as follows:

•  Safety door monitoring to ISO 14119

•  Position switches with positive break to IEC/EN 60947-5-1

•  Safety sensors to EN 60947-5-3

•  Emergency stop command devices to DIN EN ISO 13850 (EN 418) 

and EN 60947-5-5

•  Magnetic safety sensors to EN 60947-5-3

•  Safety light curtain and photoelectric barriers according to  

EN IEC 61496

• Two-hand control panels to ISO 13851 type IIIA and IIIC

The connection of magnetic safety switches to the SRB-E-... 

safety-monitoring module is only admitted when the 

requirements of the standard IEC 60947-5-3 are observed.

As the technical data are regarded, the following minimum 

requirements must be met:

• Switching capacity: min. 240 mW

• Switching voltage: min. 24 VDC

• Switching current: min. 10 mA

For example, the following safety sensors meet the 

requirements:

• BNS 36-02Z(G), BNS 36-02/01Z(G)

• BNS 260-02Z(G), BNS 260-02/01Z(G)

When sensors with LED are wired in the control circuit 

(protective circuit), the following rated operating voltage must 

be observed and respected:

• 24 VDC with a max. tolerance of –5%/+20%

Otherwise availability problems could occur, especially in 

series-wired sensors, where a voltage drop in the control 

circuit is triggered by LED's for instance.

7.2  Application example

Dual-channel control, shown for guard door monitoring with  

two position switches where one has a positive break contact; 

with external reset button

•  Relay outputs: Suitable for 2-channel control, for increase in capacity 

or number of contacts by means of contactors or relays with positive-

guided contacts

•  H2 = Feedback circuit

Signalling outputs must not be used in safety circuits.

6.  Diagnostic

6.1  LED indications

LED

Function

Display type

RUN

Ready for operation

Continuously lit

Not a valid application

Flashes

In 1/2

Input S12 and S22 closed

Continuously lit

Time window for synchronicity exceeded Flashes quickly
1-channel opening

Flashes slowly

In 3/4

Input S32 and S42 closed

Continuously lit

Time window for synchronicity exceeded Flashes quickly
1-channel opening

Flashes slowly

Out 1

Safety output application 1 ON

Continuously lit

Safety outputs waiting for start (input X2) Flashes slowly
Feedback circuit not closed (input X3)

Flashes slowly

Out 2

Safety outputs application 2 ON

Continuously lit

No release signal on input X7

Flashes quickly

Safety outputs waiting for start (input X4) Flashes slowly
Feedback circuit not closed (input X5)

Flashes slowly

Single flashing of all LEDs with mains on

6.2  Malfunctions

Malfunctions and fault causes are displayed with the ERR-LEDs  

via short and long flashing signals

LED Error cause

Long flash Short flash

ERR

Operating voltage too low

1

1

Operating voltage too high

1

2

Invalid rotary switch setting

1

3

External voltage on output Q1

1

5, 7, 9

External voltage on output Q2

1
2

6, 8

1

Termination to GND on output Q1

2

2

Termination to GND on output Q2

2

3

Cross-wire between inputs  
S12 and S22

2

4

Cross-wire between inputs  
S32 and S42

2

5

Undefined level on outputs:

X2

3

4

X3

3

5

X4

3

6

X5

3

7

X7

3

9

S12

2

9

S22

3

1

S32

3

2

S42

3

3

Rotary switch > 30 sec. to position C

6

8

Application changed  
and activation of  
operating voltage

LEDs flash quickly:

RUN, In 1/2, In 3/4, 

Out 1, Out 2

Application was  
changed during  
active operation

LEDs flash quickly:

In 1/2, In 3/4,  

Out 1, Out 2

Other fault codes:  
Consult technical sales dept. at Schmersal

Содержание SRB-E-402ST

Страница 1: ...e could lead to physical injury and or damage to the machine Content 1 About this document 1 1 Function 1 1 2 Target group authorised qualified personnel 1 1 3 Explanation of the symbols used 1 1 4 Ap...

Страница 2: ...elay module is to be operated in an area in which access by personnel is restricted 2 Product description 2 1 Ordering code This operating instructions manual applies to the following types SRB E 402S...

Страница 3: ...0 Inductive consumers provision is to be made for suitable protective wiring for suppression Mechanical data Connection type refer to 2 1 Cable section refer to 2 1 Connecting cable rigid or flexible...

Страница 4: ...etic Compatibility EMC of DIN EN 60204 1 4 2 Coding of connecting terminals 5 Operating principle and settings 5 1 Description of the terminals and LED indications Pin Function LED Function A1 Operati...

Страница 5: ...sition C Application 1 is deleted Lights up Flashes Flashes Flashes Flashes Setting cycle active Application 1 is deleted No valid application stored Flashes SRB E ready for new applications Select mo...

Страница 6: ...of contactors or relays with positive guided contacts H2 Feedback circuit Signalling outputs must not be used in safety circuits 6 Diagnostic 6 1 LED indications LED Function Display type RUN Ready f...

Страница 7: ...position 6 Rotary knob position 2 Rotary knob position 7 Rotary knob position 3 Rotary knob position 8 Rotary knob position 4 Rotary knob position 9 Rotary knob position 5 Rotary knob position 10 7 4...

Страница 8: ...S32 S42 S31 S41 S32 S42 S31 S41 24VDC S12 S22 Rotary knob position Function 5 Reset button detection of the trailing edge 6 Reset without monitoring autostart Two hand control type IIIC safety functi...

Страница 9: ...chine Machine n Machine type Module n Configured application mode 1 Configured application mode 2 Set on date Signature of the responsible person 8 5 Maintenance A regular visual inspection and functi...

Страница 10: ...35 EC prototype test certificate 01 205 5365 00 18 Person authorised for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal Place and date of issue Wuppertal J...

Отзывы: